End view shown

Item

Component

Description

 

 

 

1

Heat exchanger

Uses chilled facility water to cool the air in the HP POD 20c

2

Drain pan sensor

Detects excessive amounts of condensate in the drain pan and sends an alarm

 

 

signal to the ECS

 

 

 

3

Drain pan

Collects and directs heat exchanger condensate to the condensate drain

4

Condensation drain

Removes condensation from the drain tray to the exterior of the HP POD 20c

5

Header drain pan

Provides leak detection for the chilled water supply and the chilled water

 

 

supply return

 

 

 

Fans

HP POD 20c fans operate at variable speeds to maintain the following setpoints programmed in the ECS. The setpoints are maintained in the following order:

1.Differential pressure setpoint between the hot and cold aisles

2.Hot aisle temperature setpoint

The fan speed adjusts to maintain both setpoints. Do not manually adjust the fan speed.

IMPORTANT: HP recommends leaving the fans in AUTO mode during normal operation.

Cooling system 62

Page 62
Image 62
HP Performance Optimized Data Center (POD) 20cp manual Fans, End view shown Component Description