IBM DCS9550 1S1 Thermal Alarm, Thermal Shutdown, Drive Carrier Module Faults, State, Green, Amber

Models: DCS9550 1S1

1 79
Download 79 pages 24.28 Kb
Page 59
Image 59
4.5.4Thermal Alarm

Troubleshooting and Problem Solving

4.5.4Thermal Alarm

 

Symptom

Cause

 

Action

 

 

 

 

 

1

Ops Panel FAULT

If the internal

1

Check local ambient environment

 

LED AMBER.

temperature measured in

 

temperature is below the upper 40°C

2

An AMBER LED on

the airflow through the

 

specification.

enclosure exceeds a pre-

2

Check the installation for any airflow

 

one or more Power

set threshold a thermal

 

Supply/Cooling

alarm will sound.

 

restrictions at either the front or rear

 

Modules.

 

 

of the enclosure. A minimum gap of

 

 

 

 

25mm at the front and 50mm at the

3

Audible Alarm

 

 

rear is recommended.

 

Sounding.

 

 

 

4

Air temperature

 

3

Check for restrictions due to dust

 

 

build-up, clean as appropriate.

 

exiting PSU above

 

 

 

 

55°C.

 

4

Check for excessive re-circulation of

 

 

 

 

heated air from rear to the front, use

 

 

 

 

in a fully enclosed rack installation is

 

 

 

 

not recommended.

 

 

 

5

If possible shutdown the enclosure

 

 

 

 

and investigate the problem before

 

 

 

 

continuing.

 

 

 

 

 

4.5.5Thermal Shutdown

Important For thermal warnings please refer to the SES specification.

An Enclosure will shut down when a critical temperature threshold is exceeded in order to prevent permanent damage to the disk drives.

4.6Drive Carrier Module Faults

Disk drive status is monitored by a Green LED and an Amber LED mounted on the front of each Drive Carrier Module, providing the following indications:

Table 4–4LED Functions

State

Green

Amber

 

 

 

No drive fitted

Off

Off

 

 

 

Drive Power ON

On

Off

 

 

 

Drive Activity

On/Blink off

Off

 

 

 

Drive Fault

On

On

 

 

 

Drive activity - LED may be off for a length of time during power up.

44

IBM System Storage DCS9550 1S1 Storage Expansion Unit Installation, Service, and User Guide

Page 59
Image 59
IBM DCS9550 1S1 manual Thermal Alarm, Thermal Shutdown, Drive Carrier Module Faults, State, Green, Amber, Cause