IBM DCS9550 1S1 manual Troubleshooting, System Faults, Power Supply/Cooling Faults, Symptom, Cause

Models: DCS9550 1S1

1 79
Download 79 pages 24.28 Kb
Page 57
Image 57
4.5Troubleshooting

Troubleshooting and Problem Solving

4.5Troubleshooting

The following sections describe common problems, with possible solutions, which can occur with your DCS9550 1S1 Storage Expansion Unit

4.5.1System Faults

Symptom

Cause

Action

 

 

 

1 The SYSTEM LED will

The ESI

1 Check for other AMBER LED indications on the

illuminate AMBER on

processor has

Power Supply/Cooling modules. If there is a

the SCM

detected an

PSU error present there may be a

internal fault (e.g.

 

communications problem with that Power

 

failure of an

2 Audible Alarm sound

Supply/Cooling module. Remove and then re-fit

internal

 

the module, if the problem persists then change

 

communications

 

the module.

 

path)

 

 

2 Check for other AMBER LED indications on the

 

 

drive carriers. If none are evident then there may

 

 

either be an ESI processor problem or a

 

 

Backplane problem.

 

 

3 Ops Panel module faulty. Please contact your

 

 

supplier.

 

 

 

 

 

 

Note See also Section 4.5.5.

4.5.2Power Supply/Cooling Faults

Symptom

Cause

Action

 

 

 

 

 

 

1

Ops Panel FAULT

1

Any power

1

Check Power On/Off Switch on rear of Power

 

LED AMBER

 

fault.

 

Supply/Cooling module is switched ON.(not

 

 

 

 

 

accessible on later models)

2

An AMBER LED on

2

A fan failure.

 

 

 

one or more Power

3

A thermal

2

Check AC Mains Connections to Power Supply/

 

Supply/Cooling

 

Cooling module is live.

 

Modules.

 

condition

 

 

 

 

 

which could

3

Disconnect the Power Supply/Cooling module

3

Audible Alarm

 

cause PSU

 

from mains power and remove the module from

 

Sounding.

 

overheating.

 

the system. Re-install: if problem persists,

 

 

 

 

 

replace Power Supply/Cooling Module.

 

 

 

 

4

Reduce the ambient temperature.

 

 

 

 

 

 

42

IBM System Storage DCS9550 1S1 Storage Expansion Unit Installation, Service, and User Guide

Page 57
Image 57
IBM DCS9550 1S1 manual Troubleshooting, System Faults, Power Supply/Cooling Faults, Symptom, Cause, Action