Installation
2
Installation
In this chapter, you are shown how to install your DCS9550 1S1 Storage Expansion Unit and
Caution When connecting up the DCS9550 1S1 Storage Expansion Unit, use only the power cords supplied or cords which match the specification quoted in section 1.4.5.
2.1Planning Your Installation
Before you begin installation you should become familiar with the configuration requirements of your DCS9550 1S1 Storage Expansion Unit, detailed in Table
Table | DCS9550 1S1 Storage Expansion Unit Configuration | |
|
|
|
Module |
| Location |
|
|
|
Drive Bays |
| ALL drive bays must be fitted with either a drive carrier module |
|
| or a dummy carrier, no bays should be left completely empty. |
|
| Drive carrier modules 0 & 15 provide SES Management Services. |
|
| |
Power Supply/ | Two Power Supply/Cooling modules must be fitted. Full power | |
Cooling Modules | and cooling redundancy is provided while a faulty module is | |
|
| replaced. Install the Power Supply/Cooling modules in rear Bays |
|
| 1 and 5. |
|
| Note: Rear bays are numbered from 1 to 5 commencing from the right |
|
| side. |
|
| |
SCM I/O Module | One SCM module should be installed in rear Bay 3. A blank | |
|
| module is fitted rear Bay 4. |
|
|
|
IBM System Storage DCS9550 1S1 Storage Expansion Unit Installation, Service, and User Guide | 15 |