Introduction

1.4.6Environment

Table 1–3

Ambient Temperature and Humidity

 

 

 

 

 

Temperature Range

Relative Humidity

Max. Wet Bulb

 

 

 

 

 

 

 

 

Operational

 

 

5°C to 40°C

20% to 80%

23°C

 

 

 

 

 

 

 

non-condensing

 

 

 

 

 

 

 

 

Non-Operational

 

0°C to +50°C

8% to 80%

27°C

 

 

 

 

 

 

 

non-condensing

 

 

 

 

 

 

 

 

 

Storage

 

 

1°C to +60°C

8% to 80%

29°C

 

 

 

 

 

 

 

non-condensing

 

 

 

 

 

 

 

 

 

Shipping

 

 

-40°C to +60°C

5% to 100%

29°C

 

 

 

 

 

 

 

non-precipitating

 

 

 

 

 

 

 

 

 

 

Airflow

 

 

 

System must be operated with low pressure rear exhaust installation

 

 

 

 

 

(Back pressure created by rack doors and obstacles not to exceed

 

 

 

 

 

 

5 pascals [0.5mm Water gauge])

Altitude, Operational

 

 

0 to 2133 m (0 to 7,000ft)

 

 

 

 

 

 

(10,000ft at maximum ambient of 35°C)

Altitude, Non-Operational

 

-305 to 12,192m (-1000 to 40,000ft)

Shock, Operational

 

 

Vertical axis 5g peak 1/2 sine, 10ms

Shock, Non-Operational

 

30g 10ms 1/2 sine

Vibration, Operational

 

 

0.21grms 5-500 Hz Random

Vibration, Non-Operational

 

1.04grms 2-200 Hz Random

Vibration, Relocation

 

 

0.3g 2-200 Hz sine

Acoustics

 

 

 

Less than 6.0 LwA

 

 

Orientation & Mounting

19" Rack mount (3EIA Units)

 

 

Rack Rails

 

To fit 800mm depth Racks compliant with IEC 297

Rack Characteristics

 

Back pressure not exceeding 5 pascals (0.5mm water gauge)

Safety & Approvals

 

CE, UL, cUL

 

 