YH-07 / NH-07 (Continued)
Air on |
|
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
|
| Sensible Capacity (MBh) |
| Total | Total |
|
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
|
| Return Dry Bulb (°F) |
| Capacity1 | Input |
|
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
|
| ||
| 90 |
| 85 | 80 | 75 | 70 | 65 | 90 |
| 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
| ||
|
| 77 | 94.7 | 9.0 | 46.9 |
| 37.5 | 28.0 | - | - | - | 90.2 | 10.1 | 46.3 |
| 36.9 | 27.4 | - | - | - |
|
| 72 | 87.8 | 9.1 | 60.9 |
| 51.4 | 42.0 | 32.5 | - | - | 83.4 | 10.2 | 59.7 |
| 50.2 | 40.8 | 31.3 | - | - |
2250 |
| 67 | 80.9 | 9.1 | 74.8 |
| 65.4 | 55.9 | 46.5 | 37.0 | - | 76.7 | 10.3 | 73.0 |
| 63.6 | 54.1 | 44.6 | 35.2 | - |
|
| 62 | 74.3 | 8.8 | 74.3 |
| 74.3 | 66.2 | 56.8 | 47.3 | 37.9 | 70.6 | 9.9 | 70.6 |
| 70.6 | 63.3 | 53.8 | 44.3 | 34.9 |
|
| 57 | 75.0 | 8.9 | 75.0 |
| 75.0 | 66.0 | 56.5 | 47.0 | 37.6 | 71.3 | 10.0 | 71.3 |
| 71.3 | 61.9 | 52.5 | 43.0 | 33.5 |
|
| 77 | 97.0 | 9.1 | 54.0 |
| 41.1 | 30.5 | - | - | - | 92.3 | 10.1 | 54.6 |
| 40.5 | 29.8 | - | - | - |
|
| 72 | 89.9 | 9.1 | 66.9 |
| 56.3 | 45.6 | 35.0 | - | - | 85.3 | 10.2 | 65.7 |
| 55.0 | 44.3 | 33.7 | - | - |
2625 |
| 67 | 82.8 | 9.2 | 79.8 |
| 71.4 | 60.8 | 50.2 | 39.5 | - | 78.4 | 10.3 | 76.8 |
| 69.5 | 58.9 | 48.2 | 37.5 | - |
|
| 62 | 76.1 | 8.8 | 76.1 |
| 76.1 | 72.0 | 61.4 | 50.8 | 40.1 | 72.2 | 9.9 | 72.2 |
| 72.2 | 68.9 | 58.4 | 47.5 | 36.9 |
|
| 57 | 76.8 | 9.0 | 76.8 |
| 76.8 | 71.7 | 61.1 | 50.5 | 39.8 | 72.9 | 10.1 | 72.9 |
| 72.9 | 67.4 | 57.1 | 46.1 | 35.4 |
|
| 77 | 99.2 | 9.1 | 61.1 |
| 44.7 | 32.9 | - | - | - | 94.3 | 10.2 | 62.8 |
| 44.1 | 32.2 | - | - | - |
|
| 72 | 92.0 | 9.2 | 72.9 |
| 61.1 | 49.3 | 37.5 | - | - | 87.2 | 10.3 | 71.7 |
| 59.8 | 47.9 | 36.1 | - | - |
3000 |
| 67 | 84.8 | 9.2 | 84.8 |
| 77.5 | 65.7 | 53.9 | 42.1 | - | 80.2 | 10.3 | 80.2 |
| 75.5 | 63.6 | 51.8 | 39.9 | - |
|
| 62 | 77.8 | 8.9 | 77.8 |
| 77.8 | 77.8 | 66.0 | 54.2 | 42.4 | 73.8 | 9.9 | 73.8 |
| 73.8 | 73.8 | 63.0 | 50.7 | 38.8 |
|
| 57 | 78.6 | 9.0 | 78.6 |
| 78.6 | 77.5 | 65.7 | 53.9 | 42.1 | 74.5 | 10.1 | 74.5 |
| 74.5 | 72.9 | 61.8 | 49.1 | 37.3 |
|
| 72 | 92.2 | 9.2 | 78.1 |
| 65.2 | 52.3 | 39.4 | - | - | 87.4 | 10.2 | 77.0 |
| 64.1 | 51.2 | 38.2 | - | - |
3375 |
| 67 | 84.9 | 9.2 | 84.9 |
| 81.3 | 69.7 | 56.8 | 44.0 | - | 80.3 | 10.3 | 80.3 |
| 78.9 | 67.9 | 55.0 | 42.1 | - |
| 62 | 78.0 | 8.9 | 78.0 |
| 78.0 | 78.0 | 65.1 | 52.2 | 39.3 | 74.0 | 9.9 | 74.0 |
| 74.0 | 74.0 | 61.5 | 48.4 | 35.4 | |
|
|
|
| |||||||||||||||||
|
| 57 | 78.7 | 9.0 | 78.7 |
| 78.7 | 78.2 | 65.3 | 52.4 | 39.5 | 74.6 | 10.1 | 74.6 |
| 74.6 | 73.8 | 61.3 | 47.9 | 35.0 |
|
| 72 | 92.3 | 9.1 | 83.3 |
| 69.3 | 55.4 | 41.4 | - | - | 87.5 | 10.2 | 82.4 |
| 68.4 | 54.4 | 40.4 | - | - |
3750 |
| 67 | 85.1 | 9.2 | 85.1 |
| 85.1 | 73.8 | 59.8 | 45.8 | - | 80.4 | 10.3 | 80.4 |
| 80.4 | 72.2 | 58.2 | 44.2 | - |
| 62 | 78.1 | 8.9 | 78.1 |
| 78.1 | 78.1 | 64.1 | 50.2 | 36.2 | 74.1 | 9.9 | 74.1 |
| 74.1 | 74.1 | 60.1 | 46.1 | 32.1 | |
|
|
|
| |||||||||||||||||
|
| 57 | 78.9 | 9.0 | 78.9 |
| 78.9 | 78.9 | 64.9 | 51.0 | 37.0 | 74.8 | 10.0 | 74.8 |
| 74.8 | 74.8 | 60.8 | 46.8 | 32.8 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
16 | Johnson Controls Unitary Products |