![1Minimum Circuit Ampacity.](/images/new-backgrounds/35800/35800151x1.webp)
Electrical Data - Indoor Units
|
| Supply |
|
|
|
|
| 1 | Max Fuse2/ |
|
| Blower |
| Electric Heat Option |
| MCA | |||
Motor HP | Power Supply |
|
|
| Breaker3 Size | ||||
|
| Motor |
|
|
|
| (Amps) | (Amps) | |
|
| FLA | Model | KW | Stages | Amps |
|
| |
|
|
|
|
| |||||
|
|
| NH/NJ |
|
|
|
|
| |
|
|
| None | 31.5 | 35 | ||||
| 14.0 | 20 KW | 15 | 1 | 41.7 | 73.2 | 80 | ||
| 32 KW | 24 | 2 | 66.7 | 98.2 | 100 | |||
|
|
| |||||||
|
|
| 52 KW | 39.1 | 2 | 108.4 | 139.9 | 150 | |
|
|
| None | 31.5 | 35 | ||||
| 14.0 | 20 KW | 20 | 1 | 48.1 | 79.6 | 80 | ||
| 32 KW | 32 | 2 | 77.0 | 108.5 | 110 | |||
|
|
| |||||||
5.0 |
|
| 52 KW | 52 | 2 | 125.1 | 156.6 | 175 | |
|
| None | 15.8 | 20 | |||||
|
|
| |||||||
| 7.0 | 20 KW | 20 | 1 | 24.1 | 39.8 | 40 | ||
| 32 KW | 32 | 2 | 38.5 | 54.2 | 60 | |||
|
|
| |||||||
|
|
| 52 KW | 52 | 2 | 62.5 | 78.3 | 80 | |
|
|
| None | 11.7 | 15 | ||||
| 5.2 | 20 KW | 20 | 1 | 19.2 | 30.9 | 35 | ||
| 32 KW | 32 | 2 | 30.8 | 42.5 | 45 | |||
|
|
| |||||||
|
|
| 52 KW | 52 | 2 | 50.0 | 61.7 | 70 | |
|
|
| NH/NJ |
|
|
|
|
| |
|
|
| None | 43.2 | 45 | ||||
| 19.2 | 20 KW | 15 | 1 | 41.7 | 84.9 | 90 | ||
| 32 KW | 24 | 2 | 66.7 | 109.9 | 110 | |||
|
|
| |||||||
|
|
| 52 KW | 39.1 | 2 | 108.4 | 151.6 | 175 | |
|
|
| None | 43.2 | 45 | ||||
| 19.2 | 20 KW | 20 | 1 | 48.1 | 91.3 | 100 | ||
| 32 KW | 32 | 2 | 77.0 | 120.2 | 125 | |||
|
|
| |||||||
7.5 |
|
| 52 KW | 52 | 2 | 125.1 | 168.3 | 175 | |
|
| None | 21.6 | 25 | |||||
|
|
| |||||||
| 9.6 | 20 KW | 20 | 1 | 24.1 | 45.7 | 50 | ||
| 32 KW | 32 | 2 | 38.5 | 60.1 | 70 | |||
|
|
| |||||||
|
|
| 52 KW | 52 | 2 | 62.5 | 84.1 | 90 | |
|
|
| None | 17.6 | 20 | ||||
| 7.8 | 20 KW | 20 | 1 | 19.2 | 36.8 | 40 | ||
| 32 KW | 32 | 2 | 30.8 | 48.3 | 50 | |||
|
|
| |||||||
|
|
| 52 KW | 52 | 2 | 50.0 | 67.6 | 70 |