Johnson Controls R-410A manual YH-07Thru -20and YJ-10Thru -20Physical Data

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 9
Image 9
Physical Data

505430-BTG-A-0309

Physical Data

YH-07 Thru -20 and YJ-10 Thru -20 Physical Data

Component

 

 

 

 

 

Models

 

 

 

 

 

YH-07

YH-10

YJ-10

YH-12

YJ-12

YH-15

YJ-15

YH-20

YJ-20

 

 

Nominal Tonnage

 

7.5

10

10

12.5

12.5

15

15

20

20

REFRIGERANT

 

 

 

 

 

 

 

 

 

 

Refrigerant type

 

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

R-410A

Holding charge (lb)1

 

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

Operating Charge (lb)2

System #1

4.7

6.5

3.3

9.6

4.8

10.8

5.4

12.8

6.4

System #2

---

---

3.3

---

4.8

---

5.4

---

6.4

 

DIMENSIONS (inches)

 

 

 

 

 

 

 

 

 

 

Length

 

59.1

59.1

59.1

59.1

59.1

59.1

59.1

59.1

59.1

Width

 

31.9

31.9

31.9

31.9

31.9

64.1

64.1

64.1

64.1

Height

 

44.5

50.0

50.0

50.0

50.0

44.5

44.5

50.0

50.0

WEIGHTS (lb)

 

 

 

 

 

 

 

 

 

 

Shipping

 

330

450

445

450

445

685

685

715

715

Operating

 

325

445

440

445

440

675

675

710

710

COMPRESSORS

 

 

 

 

 

 

 

 

 

 

 

 

Single

Tandem

Single

Tandem

Tandem

Tandem

Tandem

Tandem

Tandem

Type

 

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Quantity

 

1

1

2

1

1

1

1

1

1

Nominal Capacity (Tons)

System #1

7.5

10

5

12.5

6.3

15

7.5

20

10

System #2

---

---

5

---

6.3

---

7.5

---

10

 

Capacity Stages

System #1

1

2

1

2

1

2

1

2

1

System #2

---

---

1

---

1

---

1

---

1

 

SYSTEM DATA

 

 

 

 

 

 

 

 

 

 

No. Refrigeration Circuits

 

1

1

2

1

2

1

2

1

2

Suction Line OD (in.)

 

1 1/8

1 3/8

1 1/8

1 3/8

1 1/8

1 5/8

1 1/8

1 5/8

1 3/8

Liquid Line OD (in.)

 

5/8

7/8

5/8

7/8

5/8

7/8

5/8

7/8

7/8

OUTDOOR COIL DATA

 

 

 

 

 

 

 

 

 

 

Face area (Sq. Ft.)

 

23.8

29.0

29.0

29.0

29.0

47.5

47.5

58.1

58.1

Rows

 

1

1

1

1

1

1

1

1

1

Fins per inch

 

23

23

23

23

23

23

23

23

23

Tube diameter (in./MM)

 

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

0.71 / 18

Circuitry Type

 

2-pass

2-pass

2-pass

2-pass

2-pass

2-pass

2-pass

2-pass

2-pass

Refrigerant Control

 

---

---

---

---

---

---

---

---

---

CONDENSER FAN DATA

 

 

 

 

 

 

 

 

 

 

No. Fans / Diameter (in.)

 

2/24

2/24

2/24

4/24

4/24

4/24

4/24

4/24

4/24

Type

 

Axial

Axial

Axial

Axial

Axial

Axial

Axial

Axial

Axial

Drive type

 

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Direct

Direct

No. speeds

 

1

1

1

1

1

1

1

1

1

Number of motors

System #1

2

2

2

2

2

4

2

4

2

System #2

---

---

---

---

---

---

2

---

2

 

Motor HP (ea.)

 

1/3

3/4

3/4

3/4

3/4

1/3

1/3

3/4

3/4

Rotation3

 

CW

CW

CW

CW

CW

CW

CW

CW

CW

RPM

 

850

850

1100

1100

1100

850

850

1100

1100

Nominal CFM

System #1

7500

9800

9800

9800

9800

15000

7500

19600

9800

System #2

---

---

---

---

---

---

7500

---

9800

 

1Holding Charge is the amount in the unit as shipped from the factory.

2Includes matched indoor blower unit but no piping.

3When viewing the shaft end of the motor.

Johnson Controls Unitary Products

9

Page 9
Image 9