Heat Pump And Air Handler Heating Capacities
PH-07 / NH-07
Air Over Evaporator Coil | Capacity1 & |
|
| Outdoor Temperature (°F @ 72% RH) |
|
| |||||
CFM | DB (°F) | kW | 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||
| 55 | MBH | 34.0 | 39.6 | 46.2 | 53.9 | 62.9 | 73.5 | 86.0 | 100.6 | |
| KW | 4.9 | 5.3 | 5.6 | 6.0 | 6.3 | 6.7 | 7.0 | 7.3 | ||
|
| ||||||||||
2250 | 70 | MBH | 31.0 | 36.6 | 43.2 | 50.9 | 60.0 | 70.6 | 83.0 | 97.6 | |
KW | 5.8 | 6.1 | 6.5 | 6.8 | 7.1 | 7.5 | 7.8 | 8.2 | |||
|
| ||||||||||
| 80 | MBH | 28.7 | 34.3 | 40.9 | 48.6 | 57.7 | 68.3 | 80.7 | 95.3 | |
| KW | 6.4 | 6.8 | 7.1 | 7.4 | 7.8 | 8.1 | 8.5 | 8.8 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 35.3 | 40.9 | 47.5 | 55.2 | 64.3 | 74.9 | 87.3 | 101.9 | |
| KW | 4.7 | 5.1 | 5.4 | 5.8 | 6.1 | 6.5 | 6.8 | 7.1 | ||
|
| ||||||||||
3000 | 70 | MBH | 32.4 | 38.0 | 44.5 | 52.3 | 61.3 | 71.9 | 84.4 | 99.0 | |
KW | 5.6 | 5.9 | 6.3 | 6.6 | 6.9 | 7.3 | 7.6 | 8.0 | |||
|
| ||||||||||
| 80 | MBH | 30.1 | 35.7 | 42.3 | 50.0 | 59.0 | 69.6 | 82.1 | 96.7 | |
| KW | 6.2 | 6.5 | 6.9 | 7.2 | 7.6 | 7.9 | 8.3 | 8.6 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 36.6 | 42.2 | 48.8 | 56.5 | 65.6 | 76.2 | 88.6 | 103.2 | |
| KW | 5.2 | 5.6 | 5.9 | 6.3 | 6.6 | 7.0 | 7.3 | 7.6 | ||
|
| ||||||||||
3750 | 70 | MBH | 33.7 | 39.3 | 45.8 | 53.6 | 62.6 | 73.2 | 85.7 | 100.3 | |
KW | 6.1 | 6.4 | 6.8 | 7.1 | 7.4 | 7.8 | 8.1 | 8.5 | |||
|
| ||||||||||
| 80 | MBH | 31.4 | 37.0 | 43.6 | 51.3 | 60.3 | 70.9 | 83.4 | 98.0 | |
| KW | 6.7 | 7.0 | 7.4 | 7.7 | 8.1 | 8.4 | 8.8 | 9.1 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
Air Over Evaporator Coil | Capacity1 & |
|
| Outdoor Temperature (°F @ 72% RH) |
|
| |||||
CFM | DB (°F) | kW | 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||
| 55 | MBH | 29.1 | 36.4 | 45.3 | 56.0 | 69.0 | 84.7 | 103.8 | 126.8 | |
| KW | 6.9 | 7.3 | 7.6 | 8.0 | 8.3 | 8.7 | 9.1 | 9.4 | ||
|
| ||||||||||
3000 | 70 | MBH | 26.3 | 33.6 | 42.4 | 53.1 | 66.1 | 81.8 | 100.9 | 124.0 | |
KW | 8.2 | 8.6 | 8.9 | 9.3 | 9.7 | 10.0 | 10.4 | 10.7 | |||
|
| ||||||||||
| 80 | MBH | 24.2 | 31.5 | 40.4 | 51.1 | 64.1 | 79.8 | 98.8 | 121.9 | |
| KW | 9.2 | 9.6 | 10.0 | 10.3 | 10.7 | 11.1 | 11.4 | 11.8 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 37.4 | 44.7 | 53.5 | 64.3 | 77.2 | 93.0 | 112.0 | 135.1 | |
| KW | 6.7 | 7.1 | 7.4 | 7.8 | 8.1 | 8.5 | 8.9 | 9.2 | ||
|
| ||||||||||
4000 | 70 | MBH | 34.5 | 41.8 | 50.7 | 61.4 | 74.4 | 90.1 | 109.2 | 132.2 | |
KW | 8.0 | 8.4 | 8.7 | 9.1 | 9.5 | 9.8 | 10.2 | 10.6 | |||
|
| ||||||||||
| 80 | MBH | 32.5 | 39.8 | 48.6 | 59.3 | 72.3 | 88.0 | 107.1 | 130.2 | |
| KW | 9.0 | 9.4 | 9.8 | 10.1 | 10.5 | 10.9 | 11.2 | 11.6 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 44.1 | 51.4 | 60.3 | 71.0 | 84.0 | 99.7 | 118.7 | 141.8 | |
| KW | 6.9 | 7.2 | 7.6 | 8.0 | 8.3 | 8.7 | 9.0 | 9.4 | ||
|
| ||||||||||
5000 | 70 | MBH | 41.3 | 48.6 | 57.4 | 68.1 | 81.1 | 96.8 | 115.9 | 138.9 | |
KW | 8.2 | 8.6 | 8.9 | 9.3 | 9.6 | 10.0 | 10.4 | 10.7 | |||
|
| ||||||||||
| 80 | MBH | 39.2 | 46.5 | 55.3 | 66.1 | 79.0 | 94.8 | 113.8 | 136.9 | |
| KW | 9.2 | 9.6 | 9.9 | 10.3 | 10.7 | 11.0 | 11.4 | 11.7 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
58 | Johnson Controls Unitary Products |