505430-BTG-A-0309

Electrical Data - Outdoor Unit - HP Without Powered Convenience Outlet

 

 

Compressors

 

 

Outdoor Fan Motor

Pwr Conv

Minimum

Maximum

 

 

 

 

Outlet

Model

 

 

 

 

 

 

 

 

Circuit

Fuse Size

 

Power

Qty.

RLA

MCC

LRA

Qty

FLA

FLA

Ampacity1

(A)2

 

Supply

 

(each)

(each)

(each)

 

(each)

 

 

 

 

208/230-3-60

1

25.0

39

164

2

2.1

0.0

35.5

45

 

 

 

 

 

 

 

 

 

 

 

PH-07

460-3-60

1

12.2

19

100

2

1.2

0.0

17.6

25

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

1

9.0

14

78

2

0.9

0.0

13.1

20

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

15.6

24

110

2

3.0

0.0

41.2

50

 

 

 

 

 

 

 

 

 

 

 

PH-10

460-3-60

2

7.8

12

52

2

1.6

0.0

20.8

25

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

5.8

9

39

2

1.4

0.0

15.8

20

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

0.0

64.7

80

 

 

 

 

 

 

 

 

 

 

 

PH-15

460-3-60

2

12.2

19

100

4

1.2

0.0

32.2

40

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

0.0

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

0.0

64.7

80

 

 

 

 

 

 

 

 

 

 

 

PJ-15

460-3-60

2

12.2

19

100

4

1.2

0.0

32.2

40

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

0.0

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

0.0

79.8

100

 

 

 

 

 

 

 

 

 

 

 

PH-20

460-3-60

2

16.7

26

114

4

1.6

0.0

44.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

0.0

32.9

45

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

0.0

79.8

100

 

 

 

 

 

 

 

 

 

 

 

PJ-20

460-3-60

2

16.7

26

114

4

1.6

0.0

44.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

0.0

32.9

45

 

 

 

 

 

 

 

 

 

 

 

1Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Electrical Data - Outdoor Unit - HP With Powered Convenience Outlet

 

 

Compressors

 

 

Outdoor Fan Motor

Pwr Conv

Minimum

Maximum

 

 

 

 

Outlet

Model

 

 

 

 

 

 

 

 

Circuit

Fuse Size

 

Power

Qty.

RLA

MCC

LRA

Qty

FLA

FLA

Ampacity1

(A)2

 

Supply

 

(each)

(each)

(each)

 

(each)

 

 

 

 

208/230-3-60

1

25.0

39

164

2

2.1

10.0

45.5

60

 

 

 

 

 

 

 

 

 

 

 

PH-07

460-3-60

1

12.2

19

100

2

1.2

5.0

22.6

30

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

1

9.0

14

78

2

0.9

4.0

17.1

25

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

15.6

24

110

2

3.0

10.0

51.2

60

 

 

 

 

 

 

 

 

 

 

 

PH-10

460-3-60

2

7.8

12

52

2

1.6

5.0

25.8

30

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

5.8

9

39

2

1.4

4.0

19.8

25

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

PH-15

460-3-60

2

12.2

19

100

4

1.2

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

PJ-15

460-3-60

2

12.2

19

100

4

1.2

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

PH-20

460-3-60

2

16.7

28

114

4

1.6

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

PJ-20

460-3-60

2

16.7

26

114

4

1.6

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

1Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

Johnson Controls Unitary Products

73