YH-07 / NH-10 (Continued)
| Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
|
| Sensible Capacity (MBh) |
| Total | Total |
|
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
|
| Return Dry Bulb (°F) |
| Capacity1 | Input |
|
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
|
| ||
| 90 |
| 85 | 80 | 75 | 70 | 65 | 90 |
| 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 103.1 | 9.1 | 48.5 |
| 39.5 | 30.4 | - | - | - | 98.9 | 10.1 | 47.1 |
| 38.0 | 29.0 | - | - | - |
|
| 72 | 95.4 | 9.0 | 61.2 |
| 52.1 | 43.1 | 34.0 | - | - | 91.6 | 9.9 | 59.8 |
| 50.7 | 41.7 | 32.6 | - | - |
2250 |
| 67 | 87.6 | 8.9 | 73.9 |
| 64.8 | 55.8 | 46.7 | 37.6 | - | 84.4 | 9.8 | 72.5 |
| 63.4 | 54.4 | 45.3 | 36.2 | - |
|
| 62 | 80.6 | 8.7 | 80.6 |
| 77.7 | 68.6 | 59.5 | 50.4 | 41.4 | 77.2 | 9.7 | 77.2 |
| 76.0 | 67.0 | 57.9 | 48.8 | 39.8 |
|
| 57 | 79.5 | 8.6 | 79.5 |
| 79.5 | 72.1 | 63.0 | 54.0 | 44.9 | 76.6 | 9.5 | 76.6 |
| 76.6 | 69.3 | 60.2 | 51.2 | 42.1 |
|
| 77 | 106.1 | 9.2 | 52.6 |
| 42.4 | 32.2 | - | - | - | 102.1 | 10.2 | 51.2 |
| 41.0 | 30.8 | - | - | - |
|
| 72 | 98.2 | 9.1 | 66.0 |
| 55.9 | 45.7 | 35.5 | - | - | 94.6 | 10.1 | 64.7 |
| 54.5 | 44.3 | 34.2 | - | - |
2625 |
| 67 | 90.3 | 9.0 | 79.5 |
| 69.3 | 59.1 | 49.0 | 38.8 | - | 87.1 | 9.9 | 78.2 |
| 68.0 | 57.8 | 47.7 | 37.5 | - |
|
| 62 | 83.0 | 8.8 | 83.0 |
| 81.5 | 72.8 | 62.6 | 52.4 | 42.3 | 79.7 | 9.8 | 79.7 |
| 79.3 | 71.2 | 61.2 | 50.9 | 40.7 |
|
| 57 | 81.8 | 8.7 | 81.8 |
| 81.8 | 76.5 | 66.3 | 56.2 | 46.0 | 79.0 | 9.6 | 79.0 |
| 79.0 | 73.7 | 63.8 | 53.4 | 43.2 |
|
| 77 | 109.2 | 9.3 | 56.6 |
| 45.3 | 34.1 | - | - | - | 105.3 | 10.3 | 55.2 |
| 44.0 | 32.7 | - | - | - |
|
| 72 | 101.0 | 9.2 | 70.8 |
| 59.6 | 48.3 | 37.0 | - | - | 97.5 | 10.2 | 69.5 |
| 58.3 | 47.0 | 35.7 | - | - |
3000 |
| 67 | 92.9 | 9.1 | 85.1 |
| 73.8 | 62.5 | 51.3 | 40.0 | - | 89.8 | 10.1 | 83.9 |
| 72.6 | 61.3 | 50.0 | 38.7 | - |
|
| 62 | 85.4 | 8.9 | 85.4 |
| 85.4 | 76.9 | 65.7 | 54.4 | 43.1 | 82.2 | 10.0 | 82.2 |
| 82.2 | 75.5 | 64.5 | 53.0 | 41.7 |
|
| 57 | 84.2 | 8.8 | 84.2 |
| 84.2 | 80.9 | 69.6 | 58.4 | 47.1 | 81.5 | 9.8 | 81.5 |
| 81.5 | 78.2 | 67.4 | 55.6 | 44.3 |
|
| 72 | 103.1 | 9.2 | 75.2 |
| 62.9 | 50.7 | 38.4 | - | - | 99.4 | 10.2 | 73.9 |
| 61.6 | 49.3 | 37.1 | - | - |
3375 |
| 67 | 94.7 | 9.1 | 90.1 |
| 77.8 | 65.6 | 53.3 | 41.1 | - | 91.5 | 10.1 | 88.9 |
| 76.6 | 64.4 | 52.1 | 39.8 | - |
| 62 | 87.1 | 9.0 | 87.1 |
| 87.1 | 80.7 | 68.4 | 56.2 | 43.9 | 83.7 | 10.0 | 83.7 |
| 83.7 | 79.3 | 67.2 | 54.7 | 42.5 | |
|
|
|
| |||||||||||||||||
|
| 57 | 85.9 | 8.8 | 85.9 |
| 85.9 | 84.2 | 72.0 | 59.7 | 47.5 | 83.0 | 9.8 | 83.0 |
| 83.0 | 81.4 | 69.4 | 56.8 | 44.6 |
|
| 72 | 105.1 | 9.2 | 79.5 |
| 66.2 | 53.0 | 39.8 | - | - | 101.3 | 10.2 | 78.2 |
| 64.9 | 51.7 | 38.4 | - | - |
3750 |
| 67 | 96.6 | 9.1 | 95.1 |
| 81.9 | 68.6 | 55.4 | 42.1 | - | 93.2 | 10.1 | 93.2 |
| 80.7 | 67.4 | 54.2 | 40.9 | - |
| 62 | 88.8 | 9.0 | 88.8 |
| 88.8 | 84.4 | 71.2 | 57.9 | 44.7 | 85.3 | 10.0 | 85.3 |
| 85.3 | 83.1 | 69.8 | 56.5 | 43.3 | |
|
|
|
| |||||||||||||||||
|
| 57 | 87.6 | 8.8 | 87.6 |
| 87.6 | 87.6 | 74.3 | 61.1 | 47.8 | 84.6 | 9.8 | 84.6 |
| 84.6 | 84.6 | 71.3 | 58.1 | 44.8 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
18 | Johnson Controls Unitary Products |