Johnson Controls R-410A manual YJ-10 / NJ-10 Continued

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 22
Image 22
YJ-10 / NJ-10 (Continued)

505430-BTG-A-0309

YJ-10 / NJ-10 (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

116.8

12.1

58.7

46.2

33.7

-

-

-

111.5

13.3

57.0

44.4

31.8

-

-

-

 

 

72

106.7

11.9

75.9

63.4

50.9

38.4

-

-

100.7

13.2

73.6

61.1

48.5

35.9

-

-

3000

 

67

96.6

11.8

93.2

80.7

68.2

55.7

43.2

-

89.9

13.1

89.9

77.7

65.1

52.6

40.0

-

 

 

62

89.7

11.7

89.7

89.7

83.3

70.8

58.3

45.8

84.4

12.9

84.4

84.4

80.0

67.5

54.9

42.3

 

 

57

93.0

11.7

93.0

92.9

80.4

67.9

55.4

42.9

87.9

12.9

87.9

87.9

75.5

62.9

50.3

37.8

 

 

77

122.7

12.1

71.5

52.0

37.7

-

-

-

116.2

13.3

72.4

50.2

35.8

-

-

-

 

 

72

112.1

11.9

85.6

71.3

57.0

42.7

-

-

105.0

13.2

83.3

68.9

54.5

40.1

-

-

3500

 

67

101.4

11.8

99.7

90.6

76.3

62.0

47.7

-

93.7

13.1

93.7

87.6

73.2

58.8

44.4

-

 

 

62

94.2

11.7

94.2

94.2

93.2

78.9

64.6

50.3

88.0

12.9

88.0

88.0

88.0

75.8

61.1

46.7

 

 

57

97.7

11.7

97.7

97.6

90.0

75.7

61.4

47.1

91.5

13.0

91.5

91.5

84.8

70.9

56.0

41.6

 

 

77

128.6

12.1

84.3

57.8

41.7

-

-

-

120.9

13.3

87.7

56.0

39.7

-

-

-

 

 

72

117.4

11.9

95.3

79.2

63.1

46.9

-

-

109.2

13.2

93.0

76.8

60.5

44.2

-

-

4000

 

67

106.3

11.8

106.3

100.5

84.4

68.3

52.2

-

97.4

13.1

97.4

97.4

81.3

65.0

48.8

-

 

 

62

98.8

11.7

98.8

98.8

103.1

87.0

70.9

54.8

91.5

12.9

91.5

91.5

91.5

84.2

67.3

51.1

 

 

57

102.3

11.7

102.3

102.3

99.6

83.5

67.3

51.2

95.2

13.0

95.2

95.2

94.2

78.8

61.7

45.4

 

 

72

122.9

12.0

103.0

85.3

67.6

49.9

-

-

114.7

13.2

100.8

82.9

65.0

47.0

-

-

4500

 

67

111.2

11.8

111.2

108.2

90.5

72.8

55.1

-

102.4

13.1

102.4

102.4

87.3

69.3

51.4

-

 

62

103.3

11.7

103.3

103.3

105.5

87.8

70.1

52.4

96.1

12.9

96.1

96.1

96.1

82.6

64.4

46.5

 

 

 

 

57

107.1

11.7

107.1

107.1

105.7

88.0

70.3

52.6

100.0

13.0

100.0

100.0

99.5

82.0

63.6

45.7

 

 

72

128.3

12.0

110.8

91.5

72.2

52.9

-

-

120.2

13.3

108.7

89.0

69.4

49.8

-

-

5000

 

67

116.1

11.9

116.1

115.9

96.6

77.3

58.0

-

107.3

13.2

107.3

107.3

93.3

73.7

54.1

-

 

62

107.9

11.7

107.9

107.9

107.9

88.6

69.3

50.0

100.7

13.0

100.7

100.7

100.7

81.1

61.5

41.9

 

 

 

 

57

111.8

11.8

111.8

111.8

111.8

92.5

73.2

53.9

104.8

13.0

104.8

104.8

104.8

85.2

65.6

46.0

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.