Johnson Controls R-410A manual YJ-15 / NJ-20 Continued, Sensible Capacity MBh1

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 38
Image 38
YJ-15 / NJ-20 (Continued)

505430-BTG-A-0309

YJ-15 / NJ-20 (Continued)

Air on

 

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

Sensible Capacity (MBh)1

 

 

Total

Total

 

Sensible Capacity (MBh)1

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

 

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

200.6

18.3

104.5

85.3

 

66.0

-

-

-

195.5

20.2

102.5

83.2

64.0

-

-

-

 

 

72

186.0

17.8

129.7

110.5

 

91.2

72.0

-

-

181.6

19.6

127.9

108.6

89.4

70.1

-

-

4500

 

67

171.4

17.4

154.9

135.7

 

116.4

97.2

77.9

-

167.7

19.1

153.2

134.0

114.7

95.5

76.3

-

 

 

62

153.0

16.9

153.0

153.0

 

136.1

116.8

97.6

78.3

148.7

18.5

148.7

148.7

133.0

113.8

94.5

75.3

 

 

57

156.4

16.9

156.4

156.4

 

139.2

120.0

100.7

81.5

153.5

18.5

153.5

153.5

136.4

117.1

97.9

78.7

 

 

77

207.4

18.4

117.0

93.6

 

71.5

-

-

-

202.4

20.4

115.6

91.6

69.5

-

-

-

 

 

72

192.3

18.0

143.0

120.9

 

98.9

76.8

-

-

188.1

19.8

141.2

119.1

97.0

75.0

-

-

5250

 

67

177.2

17.5

169.0

148.3

 

126.2

104.1

82.0

-

173.7

19.2

166.7

146.6

124.6

102.5

80.4

-

 

 

62

158.2

17.0

158.2

158.2

 

147.5

125.4

103.3

81.2

154.0

18.7

154.0

154.0

144.4

122.5

100.2

78.2

 

 

57

161.8

17.0

161.8

161.8

 

150.9

128.8

106.7

84.6

158.9

18.7

158.9

158.9

148.1

126.3

103.9

81.9

 

 

77

214.3

18.6

129.6

102.0

 

77.1

-

-

-

209.4

20.5

128.8

99.9

75.0

-

-

-

 

 

72

198.7

18.1

156.3

131.4

 

106.5

81.6

-

-

194.5

20.0

154.5

129.6

104.7

79.8

-

-

6000

 

67

183.1

17.6

183.1

160.9

 

135.9

111.0

86.1

-

179.7

19.4

179.7

159.3

134.4

109.5

84.6

-

 

 

62

163.5

17.1

163.5

163.5

 

158.8

133.9

109.0

84.1

159.3

18.8

159.3

159.3

155.8

131.2

106.0

81.1

 

 

57

167.1

17.1

167.1

167.1

 

162.6

137.6

112.7

87.8

164.4

18.8

164.4

164.4

159.8

135.5

110.0

85.1

 

 

72

200.5

18.1

166.3

139.0

 

111.8

84.5

-

-

196.0

19.9

164.4

137.1

109.8

82.6

-

-

6750

 

67

184.7

17.6

184.7

169.9

 

142.6

115.4

88.1

-

181.0

19.4

181.0

168.3

141.0

113.8

86.5

-

 

62

164.9

17.1

164.9

164.9

 

162.6

135.4

108.1

80.8

160.4

18.8

160.4

160.4

158.7

131.6

104.2

76.9

 

 

 

 

 

57

168.6

17.1

168.6

168.6

 

166.3

139.1

111.8

84.6

165.6

18.8

165.6

165.6

163.3

136.4

108.8

81.5

 

 

72

202.3

18.1

176.2

146.6

 

117.0

87.4

-

-

197.4

19.9

174.2

144.6

115.0

85.4

-

-

7500

 

67

186.4

17.6

186.4

178.9

 

149.3

119.7

90.1

-

182.3

19.3

182.3

177.2

147.6

118.0

88.4

-

 

62

166.4

17.1

166.4

166.4

 

166.4

136.8

107.2

77.6

161.6

18.7

161.6

161.6

161.6

132.0

102.4

72.8

 

 

 

 

 

57

170.1

17.1

170.1

170.1

 

170.1

140.5

110.9

81.3

166.8

18.7

166.8

166.8

166.8

137.2

107.6

78.0

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

38