YJ-15 / NJ-20 (Continued)
Air on |
|
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total | Sensible Capacity (MBh)1 |
|
| Total | Total |
| Sensible Capacity (MBh)1 |
| |||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| |||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 |
| 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 200.6 | 18.3 | 104.5 | 85.3 |
| 66.0 | - | - | - | 195.5 | 20.2 | 102.5 | 83.2 | 64.0 | - | - | - |
|
| 72 | 186.0 | 17.8 | 129.7 | 110.5 |
| 91.2 | 72.0 | - | - | 181.6 | 19.6 | 127.9 | 108.6 | 89.4 | 70.1 | - | - |
4500 |
| 67 | 171.4 | 17.4 | 154.9 | 135.7 |
| 116.4 | 97.2 | 77.9 | - | 167.7 | 19.1 | 153.2 | 134.0 | 114.7 | 95.5 | 76.3 | - |
|
| 62 | 153.0 | 16.9 | 153.0 | 153.0 |
| 136.1 | 116.8 | 97.6 | 78.3 | 148.7 | 18.5 | 148.7 | 148.7 | 133.0 | 113.8 | 94.5 | 75.3 |
|
| 57 | 156.4 | 16.9 | 156.4 | 156.4 |
| 139.2 | 120.0 | 100.7 | 81.5 | 153.5 | 18.5 | 153.5 | 153.5 | 136.4 | 117.1 | 97.9 | 78.7 |
|
| 77 | 207.4 | 18.4 | 117.0 | 93.6 |
| 71.5 | - | - | - | 202.4 | 20.4 | 115.6 | 91.6 | 69.5 | - | - | - |
|
| 72 | 192.3 | 18.0 | 143.0 | 120.9 |
| 98.9 | 76.8 | - | - | 188.1 | 19.8 | 141.2 | 119.1 | 97.0 | 75.0 | - | - |
5250 |
| 67 | 177.2 | 17.5 | 169.0 | 148.3 |
| 126.2 | 104.1 | 82.0 | - | 173.7 | 19.2 | 166.7 | 146.6 | 124.6 | 102.5 | 80.4 | - |
|
| 62 | 158.2 | 17.0 | 158.2 | 158.2 |
| 147.5 | 125.4 | 103.3 | 81.2 | 154.0 | 18.7 | 154.0 | 154.0 | 144.4 | 122.5 | 100.2 | 78.2 |
|
| 57 | 161.8 | 17.0 | 161.8 | 161.8 |
| 150.9 | 128.8 | 106.7 | 84.6 | 158.9 | 18.7 | 158.9 | 158.9 | 148.1 | 126.3 | 103.9 | 81.9 |
|
| 77 | 214.3 | 18.6 | 129.6 | 102.0 |
| 77.1 | - | - | - | 209.4 | 20.5 | 128.8 | 99.9 | 75.0 | - | - | - |
|
| 72 | 198.7 | 18.1 | 156.3 | 131.4 |
| 106.5 | 81.6 | - | - | 194.5 | 20.0 | 154.5 | 129.6 | 104.7 | 79.8 | - | - |
6000 |
| 67 | 183.1 | 17.6 | 183.1 | 160.9 |
| 135.9 | 111.0 | 86.1 | - | 179.7 | 19.4 | 179.7 | 159.3 | 134.4 | 109.5 | 84.6 | - |
|
| 62 | 163.5 | 17.1 | 163.5 | 163.5 |
| 158.8 | 133.9 | 109.0 | 84.1 | 159.3 | 18.8 | 159.3 | 159.3 | 155.8 | 131.2 | 106.0 | 81.1 |
|
| 57 | 167.1 | 17.1 | 167.1 | 167.1 |
| 162.6 | 137.6 | 112.7 | 87.8 | 164.4 | 18.8 | 164.4 | 164.4 | 159.8 | 135.5 | 110.0 | 85.1 |
|
| 72 | 200.5 | 18.1 | 166.3 | 139.0 |
| 111.8 | 84.5 | - | - | 196.0 | 19.9 | 164.4 | 137.1 | 109.8 | 82.6 | - | - |
6750 |
| 67 | 184.7 | 17.6 | 184.7 | 169.9 |
| 142.6 | 115.4 | 88.1 | - | 181.0 | 19.4 | 181.0 | 168.3 | 141.0 | 113.8 | 86.5 | - |
| 62 | 164.9 | 17.1 | 164.9 | 164.9 |
| 162.6 | 135.4 | 108.1 | 80.8 | 160.4 | 18.8 | 160.4 | 160.4 | 158.7 | 131.6 | 104.2 | 76.9 | |
|
|
| |||||||||||||||||
|
| 57 | 168.6 | 17.1 | 168.6 | 168.6 |
| 166.3 | 139.1 | 111.8 | 84.6 | 165.6 | 18.8 | 165.6 | 165.6 | 163.3 | 136.4 | 108.8 | 81.5 |
|
| 72 | 202.3 | 18.1 | 176.2 | 146.6 |
| 117.0 | 87.4 | - | - | 197.4 | 19.9 | 174.2 | 144.6 | 115.0 | 85.4 | - | - |
7500 |
| 67 | 186.4 | 17.6 | 186.4 | 178.9 |
| 149.3 | 119.7 | 90.1 | - | 182.3 | 19.3 | 182.3 | 177.2 | 147.6 | 118.0 | 88.4 | - |
| 62 | 166.4 | 17.1 | 166.4 | 166.4 |
| 166.4 | 136.8 | 107.2 | 77.6 | 161.6 | 18.7 | 161.6 | 161.6 | 161.6 | 132.0 | 102.4 | 72.8 | |
|
|
| |||||||||||||||||
|
| 57 | 170.1 | 17.1 | 170.1 | 170.1 |
| 170.1 | 140.5 | 110.9 | 81.3 | 166.8 | 18.7 | 166.8 | 166.8 | 166.8 | 137.2 | 107.6 | 78.0 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
38 | Johnson Controls Unitary Products |