Johnson Controls R-410A NH/NJ-15Upflow and Horizontal Airflow Performance, NH/NJ-15Horizontal

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 63
Image 63
NH/NJ-15 Upflow and Horizontal Airflow Performance

505430-BTG-A-0309

NH/NJ-15 Upflow and Horizontal Airflow Performance

NH/NJ-15 Upflow

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG

 

 

 

 

 

 

 

 

(CFM)

0.2

 

0.4

 

0.6

 

0.8

 

1.0

 

1.2

 

1.4

 

1.6

 

1.8

 

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

BHP

 

Std.

3 HP &

Field Supplied Drive

 

 

 

Standard 3 HP & Drive

 

 

 

High Static 5 HP & Drive

 

 

 

4500

 

 

 

 

 

 

583

 

 

1.1

634

 

1.3

688

 

1.5

738

 

1.9

782

 

2.3

827

 

2.6

 

 

4750

 

 

 

 

 

 

592

 

 

1.2

643

 

1.4

700

 

1.8

744

 

2.1

788

 

2.4

833

 

2.7

 

 

5000

 

 

 

 

 

 

602

 

 

1.2

653

 

1.4

707

 

1.9

751

 

2.2

795

 

2.6

840

 

2.9

 

 

5250

 

 

 

 

 

 

613

 

 

1.3

664

 

1.5

716

 

2.1

759

 

2.4

804

 

2.7

848

 

3.1

 

 

5500

 

 

 

577

 

1.1

625

 

 

1.4

676

 

1.6

725

 

2.3

768

 

2.6

813

 

2.9

857

 

3.2

 

 

5750

 

 

 

590

 

1.2

638

 

 

1.4

689

 

1.7

735

 

2.5

778

 

2.8

822

 

3.1

 

 

 

 

 

6000

 

 

 

603

 

1.3

651

 

 

1.6

702

 

2.3

745

 

2.7

789

 

3.0

833

 

3.3

 

 

 

 

 

6250

 

 

 

617

 

1.5

664

 

 

1.7

714

 

2.6

757

 

2.9

801

 

3.2

845

 

3.5

 

 

 

 

 

6500

587

 

1.4

631

 

1.6

679

 

 

1.8

726

 

2.8

769

 

3.1

813

 

3.4

857

 

3.8

 

 

 

 

 

6750

601

 

1.6

645

 

1.8

693

 

 

2.0

739

 

3.0

782

 

3.4

826

 

3.7

 

 

 

 

 

 

 

 

7000

616

 

1.8

660

 

2.0

710

 

 

2.9

753

 

3.3

796

 

3.6

839

 

3.9

 

 

 

 

 

 

 

 

7250

632

 

2.1

675

 

2.3

725

 

 

3.2

767

 

3.6

810

 

3.9

854

 

4.2

 

 

 

 

 

 

 

 

7500

647

 

2.3

691

 

2.5

740

 

 

3.5

782

 

3.9

825

 

4.2

 

 

High

Static 5 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.

2.See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

NH/NJ-15 Horizontal

 

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG

 

 

 

 

 

 

 

 

 

(CFM)

0.2

 

0.4

 

0.6

 

 

0.8

 

1.0

1.2

 

1.4

 

1.6

 

1.8

 

 

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

BHP

RPM

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

RPM

 

BHP

 

Std.

3 HP &

Field Supplied Drive

 

 

 

 

 

Standard 3 HP & Drive

 

 

 

 

 

High Static 5 HP & Drive

 

4500

 

 

 

 

 

 

585

 

 

1.5

634

 

1.6

687

 

1.8

735

 

2.0

780

 

2.5

827

 

2.7

875

 

2.9

4750

 

 

 

 

 

 

595

 

 

1.6

644

 

1.7

697

 

1.9

741

 

2.4

787

 

2.7

834

 

2.9

 

 

 

5000

 

 

 

 

 

 

605

 

 

1.7

655

 

1.8

708

 

2.0

749

 

2.6

795

 

2.9

842

 

3.1

 

 

 

5250

 

 

 

 

 

 

617

 

 

1.8

666

 

2.0

719

 

2.1

757

 

2.8

804

 

3.1

851

 

3.3

 

 

 

5500

 

 

 

582

 

1.8

629

 

 

1.9

678

 

2.1

731

 

2.3

767

 

3.0

813

 

3.2

860

 

3.4

 

 

 

5750

 

 

 

594

 

1.9

642

 

 

2.1

691

 

2.2

737

 

2.4

778

 

3.2

824

 

3.4

871

 

3.7

 

 

 

6000

 

 

 

608

 

2.1

655

 

 

2.2

705

 

2.4

744

 

3.1

789

 

3.4

835

 

3.7

 

 

 

 

 

 

6250

 

 

 

622

 

2.2

670

 

 

2.4

719

 

2.6

756

 

3.3

801

 

3.6

847

 

3.9

 

 

 

 

 

 

6500

589

 

2.2

637

 

2.4

684

 

 

2.6

733

 

2.7

769

 

3.6

814

 

3.9

860

 

4.1

 

 

 

 

 

 

6750

604

 

2.4

652

 

2.6

699

 

 

2.8

738

 

3.5

782

 

3.8

827

 

4.1

873

 

4.4

 

 

 

 

 

 

7000

620

 

2.6

667

 

2.8

715

 

 

3.0

752

 

3.8

796

 

4.1

841

 

4.4

 

 

 

 

 

 

 

 

 

7250

636

 

2.8

683

 

3.0

731

 

 

3.2

766

 

4.1

811

 

4.4

856

 

4.7

 

 

 

 

 

 

 

 

 

7500

652

 

3.0

700

 

3.2

738

 

 

4.0

781

 

4.4

825

 

4.7

 

 

High

Static 5 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Airflow performance includes dry evaporator coil. See Static Resistance table for additional applications.

2.See RPM Selection table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

Johnson Controls Unitary Products