Johnson Controls R-410A manual Unit Limitations, Condenser Unit limitations

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 12
Image 12
Unit Limitations

505430-BTG-A-0309

Unit Limitations

Condenser Unit limitations

 

 

 

 

1

Outdoor DB Temp

Indoor DB Temp

Outdoor DB Temp

Indoor DB Temp

Size

Model

Unit Voltage

Applied Voltage

Cooling (°F)

Cooling (°F)

Heating (°F)

Heating (°F)

(Tons)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

Max

Min

Max

Min

Max

Min

Max

Min

 

 

 

-07

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

PH

460-3-60

432

504

125

40

86

68

70

0

80

50

(7.5)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-07

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

YH

460-3-60

432

504

125

40

86

68

-

-

-

-

(7.5)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-10

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

PH

460-3-60

432

504

125

40

86

68

70

0

80

50

(10)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-10

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

YH/YJ

460-3-60

432

504

125

40

86

68

-

-

-

-

(10)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-12

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

YH/YJ

460-3-60

432

504

125

40

86

68

-

-

-

-

(12.5)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-15

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

PH/PJ

460-3-60

432

504

125

40

86

68

70

0

80

50

(15)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-15

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

YH/YJ

460-3-60

432

504

125

40

86

68

-

-

-

-

(15)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-20

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

PH/PJ

460-3-60

432

504

125

40

86

68

70

0

80

50

(20)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-20

 

208/230-3-60

187

252

 

 

 

 

 

 

 

 

YH/YJ

460-3-60

432

504

125

40

86

68

-

-

-

-

(20)

 

575-3-60

540

630

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Rated in accordance with ARI Standard 110, Range “A” Utilization Voltage.

†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.