PH-20 / NH-20 (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 233.9 | 23.2 | 115.1 | 91.7 | 68.3 | - | - | - | 213.8 | 25.4 | 108.3 | 85.0 | 61.6 | - | - | - |
|
| 72 | 216.2 | 22.8 | 151.9 | 128.5 | 105.1 | 81.8 | - | - | 199.1 | 25.0 | 145.6 | 122.3 | 99.0 | 75.6 | - | - |
6000 |
| 67 | 198.5 | 22.4 | 188.7 | 165.3 | 141.9 | 118.6 | 95.2 | - | 184.4 | 24.6 | 182.9 | 159.6 | 136.3 | 113.0 | 89.6 | - |
|
| 62 | 187.4 | 22.2 | 187.4 | 187.4 | 172.3 | 148.9 | 125.5 | 102.1 | 174.5 | 24.3 | 174.5 | 174.5 | 162.9 | 139.5 | 116.2 | 92.9 |
|
| 57 | 189.8 | 22.0 | 189.8 | 189.8 | 168.5 | 145.1 | 121.7 | 98.3 | 176.3 | 24.0 | 176.3 | 176.3 | 156.9 | 133.6 | 110.2 | 86.9 |
|
| 77 | 241.4 | 23.4 | 135.1 | 100.9 | 74.4 | - | - | - | 221.7 | 25.6 | 132.6 | 94.5 | 67.7 | - | - | - |
|
| 72 | 223.2 | 23.0 | 167.6 | 141.0 | 114.5 | 87.9 | - | - | 206.4 | 25.2 | 162.1 | 135.4 | 108.6 | 81.9 | - | - |
7000 |
| 67 | 204.9 | 22.6 | 200.0 | 181.1 | 154.6 | 128.0 | 101.5 | - | 191.2 | 24.8 | 191.2 | 176.3 | 149.5 | 122.8 | 96.1 | - |
|
| 62 | 193.5 | 22.3 | 193.5 | 193.5 | 187.6 | 161.1 | 134.5 | 108.0 | 180.9 | 24.5 | 180.9 | 180.9 | 178.8 | 152.7 | 125.3 | 98.6 |
|
| 57 | 195.9 | 22.1 | 195.9 | 195.9 | 183.4 | 156.9 | 130.4 | 103.8 | 182.7 | 24.1 | 182.7 | 182.7 | 172.3 | 146.5 | 118.8 | 92.1 |
|
| 77 | 249.0 | 23.5 | 155.0 | 110.2 | 80.5 | - | - | - | 229.6 | 25.7 | 156.9 | 103.9 | 73.8 | - | - | - |
|
| 72 | 230.1 | 23.1 | 183.2 | 153.5 | 123.8 | 94.1 | - | - | 213.8 | 25.3 | 178.6 | 148.4 | 118.3 | 88.2 | - | - |
8000 |
| 67 | 211.3 | 22.8 | 211.3 | 196.8 | 167.2 | 137.5 | 107.8 | - | 198.0 | 24.9 | 198.0 | 192.9 | 162.8 | 132.7 | 102.5 | - |
|
| 62 | 199.5 | 22.5 | 199.5 | 199.5 | 202.9 | 173.2 | 143.5 | 113.9 | 187.3 | 24.7 | 187.3 | 187.3 | 187.3 | 165.9 | 134.4 | 104.3 |
|
| 57 | 202.0 | 22.3 | 202.0 | 202.0 | 198.4 | 168.7 | 139.0 | 109.3 | 189.2 | 24.3 | 189.2 | 189.2 | 187.6 | 159.3 | 127.4 | 97.2 |
|
| 72 | 237.2 | 23.2 | 198.2 | 165.7 | 133.2 | 100.7 | - | - | 221.3 | 25.4 | 194.3 | 161.4 | 128.6 | 95.7 | - | - |
9000 |
| 67 | 217.8 | 22.8 | 217.8 | 210.6 | 179.8 | 147.3 | 114.9 | - | 205.0 | 25.0 | 205.0 | 205.0 | 176.8 | 143.9 | 111.1 | - |
| 62 | 205.7 | 22.5 | 205.7 | 205.7 | 207.4 | 174.9 | 142.4 | 109.9 | 193.9 | 24.7 | 193.9 | 193.9 | 193.9 | 165.4 | 131.9 | 99.0 | |
|
| |||||||||||||||||
|
| 57 | 208.3 | 22.3 | 208.3 | 208.3 | 206.4 | 174.0 | 141.5 | 109.0 | 195.9 | 24.4 | 195.9 | 195.9 | 195.1 | 163.2 | 129.4 | 96.5 |
|
| 72 | 244.3 | 23.2 | 213.2 | 177.9 | 142.6 | 107.3 | - | - | 228.9 | 25.4 | 210.0 | 174.4 | 138.8 | 103.2 | - | - |
10000 |
| 67 | 224.4 | 22.9 | 224.4 | 224.4 | 192.5 | 157.2 | 121.9 | - | 211.9 | 25.1 | 211.9 | 211.9 | 190.8 | 155.2 | 119.6 | - |
| 62 | 211.8 | 22.6 | 211.8 | 211.8 | 211.8 | 176.5 | 141.3 | 106.0 | 200.5 | 24.8 | 200.5 | 200.5 | 200.5 | 164.9 | 129.3 | 93.7 | |
|
| |||||||||||||||||
|
| 57 | 214.5 | 22.4 | 214.5 | 214.5 | 214.5 | 179.2 | 143.9 | 108.6 | 202.6 | 24.4 | 202.6 | 202.6 | 202.6 | 167.0 | 131.4 | 95.8 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.