PH-07 / NH-07 Cooling Capacities (Continued)
Air on |
|
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| ||||||
Evaporator Coil | Total | Total |
|
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| |||||||||
CFM |
| WB | Capacity1 | Input |
|
| Return Dry Bulb (°F) |
|
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| ||
| 90 |
| 85 | 80 | 75 |
| 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
| |
|
| 77 | 99.8 | 8.8 | 69.7 |
| 60.3 | 50.9 | - |
| - | - | 99.1 | 9.6 | 79.9 | 70.5 | 61.0 | - | - | - |
|
| 72 | 86.5 | 8.7 | 71.4 |
| 62.0 | 52.6 | 43.1 |
| - | - | 82.7 | 9.5 | 75.2 | 65.7 | 56.3 | 46.8 | - | - |
2250 |
| 67 | 73.1 | 8.7 | 73.1 |
| 63.7 | 54.2 | 44.8 |
| 35.4 | - | 66.4 | 9.5 | 66.4 | 60.9 | 51.5 | 42.0 | 32.6 | - |
|
| 62 | 69.9 | 8.5 | 69.9 |
| 69.9 | 62.0 | 52.6 |
| 43.2 | 33.7 | 64.9 | 9.4 | 64.9 | 64.9 | 56.8 | 47.3 | 37.9 | 28.4 |
|
| 57 | 69.5 | 8.5 | 69.5 |
| 69.5 | 60.4 | 50.9 |
| 41.5 | 32.1 | 64.1 | 9.4 | 64.1 | 64.1 | 55.1 | 45.6 | 36.2 | 26.7 |
|
| 77 | 103.0 | 8.8 | 82.4 |
| 66.4 | 55.7 | - |
| - | - | 102.3 | 9.6 | 92.7 | 77.7 | 67.0 | - | - | - |
|
| 72 | 89.2 | 8.8 | 78.9 |
| 68.2 | 57.6 | 46.9 |
| - | - | 85.4 | 9.6 | 83.3 | 72.6 | 61.9 | 51.2 | - | - |
2625 |
| 67 | 75.5 | 8.7 | 75.5 |
| 70.1 | 59.4 | 48.7 |
| 38.0 | - | 68.5 | 9.6 | 68.5 | 67.4 | 56.7 | 46.0 | 35.3 | - |
|
| 62 | 72.1 | 8.6 | 72.1 |
| 72.1 | 67.9 | 57.3 |
| 46.6 | 35.9 | 67.0 | 9.4 | 67.0 | 67.0 | 62.6 | 52.1 | 41.2 | 30.5 |
|
| 57 | 71.7 | 8.6 | 71.7 |
| 71.7 | 66.1 | 55.4 |
| 44.8 | 34.1 | 66.2 | 9.4 | 66.2 | 66.2 | 60.7 | 50.3 | 39.3 | 28.6 |
|
| 77 | 106.2 | 8.9 | 95.1 |
| 72.5 | 60.5 | - |
| - | - | 105.6 | 9.7 | 105.6 | 84.9 | 73.0 | - | - | - |
|
| 72 | 92.0 | 8.8 | 86.4 |
| 74.5 | 62.6 | 50.6 |
| - | - | 88.1 | 9.6 | 88.1 | 79.4 | 67.5 | 55.5 | - | - |
3000 |
| 67 | 77.8 | 8.7 | 77.8 |
| 76.5 | 64.6 | 52.6 |
| 40.7 | - | 70.7 | 9.6 | 70.7 | 70.7 | 62.0 | 50.0 | 38.0 | - |
|
| 62 | 74.4 | 8.6 | 74.4 |
| 74.4 | 73.8 | 61.9 |
| 50.0 | 38.0 | 69.2 | 9.5 | 69.2 | 69.2 | 68.4 | 56.9 | 44.5 | 32.5 |
|
| 57 | 73.9 | 8.6 | 73.9 |
| 73.9 | 71.9 | 59.9 |
| 48.0 | 36.1 | 68.3 | 9.5 | 68.3 | 68.3 | 66.4 | 54.9 | 42.4 | 30.5 |
|
| 72 | 94.8 | 8.8 | 92.1 |
| 81.9 | 68.9 | 55.9 |
| - | - | 90.9 | 9.7 | 90.9 | 87.7 | 74.6 | 61.5 | - | - |
3375 |
| 67 | 80.2 | 8.8 | 80.2 |
| 79.6 | 71.1 | 58.1 |
| 45.1 | - | 72.9 | 9.6 | 72.9 | 72.9 | 68.7 | 55.6 | 42.5 | - |
| 62 | 76.7 | 8.6 | 76.7 |
| 76.7 | 76.4 | 63.4 |
| 50.4 | 37.4 | 71.3 | 9.5 | 71.3 | 71.3 | 71.0 | 58.1 | 44.8 | 31.7 | |
|
|
|
| |||||||||||||||||
|
| 57 | 76.2 | 8.6 | 76.2 |
| 76.2 | 75.2 | 62.2 |
| 49.2 | 36.2 | 70.4 | 9.5 | 70.4 | 70.4 | 69.5 | 56.7 | 43.3 | 30.3 |
|
| 72 | 97.7 | 8.8 | 97.7 |
| 89.3 | 75.2 | 61.1 |
| - | - | 93.7 | 9.7 | 93.7 | 93.7 | 81.8 | 67.6 | - | - |
3750 |
| 67 | 82.6 | 8.8 | 82.6 |
| 82.6 | 77.7 | 63.6 |
| 49.5 | - | 75.2 | 9.6 | 75.2 | 75.2 | 75.2 | 61.2 | 47.0 | - |
| 62 | 79.0 | 8.7 | 79.0 |
| 79.0 | 79.0 | 64.9 |
| 50.8 | 36.7 | 73.5 | 9.5 | 73.5 | 73.5 | 73.5 | 59.3 | 45.2 | 31.0 | |
|
|
|
| |||||||||||||||||
|
| 57 | 78.5 | 8.6 | 78.5 |
| 78.5 | 78.5 | 64.4 |
| 50.3 | 36.3 | 72.6 | 9.5 | 72.6 | 72.6 | 72.6 | 58.4 | 44.2 | 30.0 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products | 47 |