PH-07 / NH-07 Cooling Capacities (Continued)

505430-BTG-A-0309

PH-07 / NH-07 Cooling Capacities (Continued)

Air on

 

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

 

Return Dry Bulb (°F)

 

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

 

85

80

75

 

70

65

90

85

80

75

70

65

 

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

99.8

8.8

69.7

 

60.3

50.9

-

 

-

-

99.1

9.6

79.9

70.5

61.0

-

-

-

 

 

72

86.5

8.7

71.4

 

62.0

52.6

43.1

 

-

-

82.7

9.5

75.2

65.7

56.3

46.8

-

-

2250

 

67

73.1

8.7

73.1

 

63.7

54.2

44.8

 

35.4

-

66.4

9.5

66.4

60.9

51.5

42.0

32.6

-

 

 

62

69.9

8.5

69.9

 

69.9

62.0

52.6

 

43.2

33.7

64.9

9.4

64.9

64.9

56.8

47.3

37.9

28.4

 

 

57

69.5

8.5

69.5

 

69.5

60.4

50.9

 

41.5

32.1

64.1

9.4

64.1

64.1

55.1

45.6

36.2

26.7

 

 

77

103.0

8.8

82.4

 

66.4

55.7

-

 

-

-

102.3

9.6

92.7

77.7

67.0

-

-

-

 

 

72

89.2

8.8

78.9

 

68.2

57.6

46.9

 

-

-

85.4

9.6

83.3

72.6

61.9

51.2

-

-

2625

 

67

75.5

8.7

75.5

 

70.1

59.4

48.7

 

38.0

-

68.5

9.6

68.5

67.4

56.7

46.0

35.3

-

 

 

62

72.1

8.6

72.1

 

72.1

67.9

57.3

 

46.6

35.9

67.0

9.4

67.0

67.0

62.6

52.1

41.2

30.5

 

 

57

71.7

8.6

71.7

 

71.7

66.1

55.4

 

44.8

34.1

66.2

9.4

66.2

66.2

60.7

50.3

39.3

28.6

 

 

77

106.2

8.9

95.1

 

72.5

60.5

-

 

-

-

105.6

9.7

105.6

84.9

73.0

-

-

-

 

 

72

92.0

8.8

86.4

 

74.5

62.6

50.6

 

-

-

88.1

9.6

88.1

79.4

67.5

55.5

-

-

3000

 

67

77.8

8.7

77.8

 

76.5

64.6

52.6

 

40.7

-

70.7

9.6

70.7

70.7

62.0

50.0

38.0

-

 

 

62

74.4

8.6

74.4

 

74.4

73.8

61.9

 

50.0

38.0

69.2

9.5

69.2

69.2

68.4

56.9

44.5

32.5

 

 

57

73.9

8.6

73.9

 

73.9

71.9

59.9

 

48.0

36.1

68.3

9.5

68.3

68.3

66.4

54.9

42.4

30.5

 

 

72

94.8

8.8

92.1

 

81.9

68.9

55.9

 

-

-

90.9

9.7

90.9

87.7

74.6

61.5

-

-

3375

 

67

80.2

8.8

80.2

 

79.6

71.1

58.1

 

45.1

-

72.9

9.6

72.9

72.9

68.7

55.6

42.5

-

 

62

76.7

8.6

76.7

 

76.7

76.4

63.4

 

50.4

37.4

71.3

9.5

71.3

71.3

71.0

58.1

44.8

31.7

 

 

 

 

 

 

57

76.2

8.6

76.2

 

76.2

75.2

62.2

 

49.2

36.2

70.4

9.5

70.4

70.4

69.5

56.7

43.3

30.3

 

 

72

97.7

8.8

97.7

 

89.3

75.2

61.1

 

-

-

93.7

9.7

93.7

93.7

81.8

67.6

-

-

3750

 

67

82.6

8.8

82.6

 

82.6

77.7

63.6

 

49.5

-

75.2

9.6

75.2

75.2

75.2

61.2

47.0

-

 

62

79.0

8.7

79.0

 

79.0

79.0

64.9

 

50.8

36.7

73.5

9.5

73.5

73.5

73.5

59.3

45.2

31.0

 

 

 

 

 

 

57

78.5

8.6

78.5

 

78.5

78.5

64.4

 

50.3

36.3

72.6

9.5

72.6

72.6

72.6

58.4

44.2

30.0

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.