Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 175.1 | 17.7 | 89.8 | 71.1 | 52.5 | - | - | - | 161.0 | 19.4 | 84.1 | 65.6 | 47.1 | - | - | - |
|
| 72 | 163.9 | 17.4 | 117.8 | 99.2 | 80.6 | 61.9 | - | - | 152.2 | 19.1 | 113.1 | 94.6 | 76.1 | 57.6 | - | - |
4500 |
| 67 | 152.8 | 17.2 | 145.9 | 127.3 | 108.6 | 90.0 | 71.4 | - | 143.4 | 18.9 | 142.1 | 123.6 | 105.1 | 86.6 | 68.0 | - |
|
| 62 | 144.6 | 17.1 | 144.6 | 144.6 | 134.7 | 116.0 | 97.4 | 78.8 | 135.8 | 18.8 | 135.8 | 135.8 | 128.1 | 109.5 | 91.0 | 72.5 |
|
| 57 | 146.8 | 17.0 | 146.8 | 146.8 | 141.1 | 122.5 | 103.9 | 85.2 | 136.8 | 18.7 | 136.8 | 136.8 | 136.6 | 118.0 | 99.5 | 81.0 |
|
| 77 | 181.4 | 17.7 | 106.1 | 78.6 | 57.4 | - | - | - | 167.8 | 19.4 | 103.6 | 73.2 | 52.2 | - | - | - |
|
| 72 | 169.9 | 17.5 | 130.5 | 109.3 | 88.1 | 66.9 | - | - | 158.6 | 19.2 | 126.2 | 105.2 | 84.1 | 63.1 | - | - |
5250 |
| 67 | 158.3 | 17.2 | 154.9 | 140.0 | 118.8 | 97.6 | 76.4 | - | 149.4 | 18.9 | 148.7 | 137.1 | 116.1 | 95.1 | 74.0 | - |
|
| 62 | 149.8 | 17.1 | 149.8 | 149.8 | 147.3 | 126.1 | 104.9 | 83.7 | 141.5 | 18.9 | 141.5 | 141.5 | 141.5 | 120.9 | 99.5 | 78.5 |
|
| 57 | 152.1 | 17.0 | 152.1 | 152.1 | 154.3 | 133.1 | 112.0 | 90.8 | 142.5 | 18.7 | 142.5 | 142.5 | 142.5 | 130.2 | 108.8 | 87.8 |
|
| 77 | 187.8 | 17.8 | 122.4 | 86.1 | 62.3 | - | - | - | 174.5 | 19.4 | 123.1 | 80.8 | 57.2 | - | - | - |
|
| 72 | 175.8 | 17.5 | 143.1 | 119.4 | 95.6 | 71.9 | - | - | 164.9 | 19.2 | 139.2 | 115.7 | 92.2 | 68.6 | - | - |
6000 |
| 67 | 163.9 | 17.3 | 163.9 | 152.7 | 129.0 | 105.2 | 81.5 | - | 155.3 | 19.0 | 155.3 | 150.7 | 127.1 | 103.6 | 80.0 | - |
|
| 62 | 155.1 | 17.2 | 155.1 | 155.1 | 159.9 | 136.1 | 112.4 | 88.7 | 147.1 | 18.9 | 147.1 | 147.1 | 147.1 | 132.2 | 108.0 | 84.4 |
|
| 57 | 157.5 | 17.1 | 157.5 | 157.5 | 167.5 | 143.8 | 120.1 | 96.3 | 148.2 | 18.8 | 148.2 | 148.2 | 148.2 | 142.4 | 118.1 | 94.6 |
|
| 72 | 174.6 | 17.6 | 153.0 | 127.0 | 101.1 | 75.1 | - | - | 162.6 | 19.2 | 149.2 | 123.1 | 97.0 | 71.0 | - | - |
6750 |
| 67 | 162.8 | 17.3 | 162.8 | 157.2 | 136.3 | 110.3 | 84.3 | - | 153.2 | 19.0 | 153.2 | 152.4 | 133.9 | 107.8 | 81.8 | - |
| 62 | 154.0 | 17.2 | 154.0 | 154.0 | 156.4 | 130.5 | 104.5 | 78.5 | 145.1 | 19.0 | 145.1 | 145.1 | 145.1 | 123.3 | 96.9 | 70.9 | |
|
| |||||||||||||||||
|
| 57 | 156.4 | 17.1 | 156.4 | 156.4 | 161.4 | 135.5 | 109.5 | 83.5 | 146.1 | 18.8 | 146.1 | 146.1 | 146.1 | 128.9 | 102.5 | 76.4 |
|
| 72 | 173.5 | 17.6 | 162.9 | 134.7 | 106.5 | 78.3 | - | - | 160.3 | 19.3 | 159.1 | 130.5 | 101.9 | 73.3 | - | - |
7500 |
| 67 | 161.7 | 17.3 | 161.7 | 161.7 | 143.6 | 115.4 | 87.2 | - | 151.0 | 19.0 | 151.0 | 151.0 | 140.6 | 112.0 | 83.5 | - |
| 62 | 153.0 | 17.2 | 153.0 | 153.0 | 153.0 | 124.8 | 96.6 | 68.4 | 143.0 | 19.0 | 143.0 | 143.0 | 143.0 | 114.5 | 85.9 | 57.3 | |
|
| |||||||||||||||||
|
| 57 | 155.4 | 17.1 | 155.4 | 155.4 | 155.4 | 127.2 | 99.0 | 70.8 | 144.0 | 18.8 | 144.0 | 144.0 | 144.0 | 115.5 | 86.9 | 58.3 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
⎟nameplate rated motorPerformance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
efficiency.
2. These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
36 | Johnson Controls Unitary Products |