YJ-15 / Two NH-07 (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 193.0 | 17.7 | 96.7 | 79.6 | 62.4 | - | - | - | 188.7 | 19.3 | 94.6 | 77.5 | 60.3 | - | - | - |
|
| 72 | 179.5 | 17.4 | 121.8 | 104.6 | 87.5 | 70.3 | - | - | 175.3 | 19.0 | 119.9 | 102.7 | 85.5 | 68.3 | - | - |
4500 |
| 67 | 166.0 | 17.1 | 146.9 | 129.7 | 112.6 | 95.4 | 78.2 | - | 161.9 | 18.7 | 145.1 | 127.9 | 110.7 | 93.5 | 76.4 | - |
|
| 62 | 154.6 | 16.8 | 154.6 | 154.6 | 137.6 | 120.4 | 103.3 | 86.1 | 152.9 | 18.5 | 152.9 | 152.9 | 136.1 | 118.9 | 101.7 | 84.6 |
|
| 57 | 151.8 | 16.8 | 151.8 | 151.8 | 136.4 | 119.2 | 102.1 | 84.9 | 148.2 | 18.4 | 148.2 | 148.2 | 132.2 | 115.1 | 97.9 | 80.7 |
|
| 77 | 198.9 | 17.8 | 105.2 | 86.0 | 66.7 | - | - | - | 193.8 | 19.4 | 103.0 | 83.7 | 64.5 | - | - | - |
|
| 72 | 185.0 | 17.5 | 132.0 | 112.8 | 93.6 | 74.3 | - | - | 180.0 | 19.1 | 129.9 | 110.7 | 91.5 | 72.2 | - | - |
5250 |
| 67 | 171.0 | 17.2 | 158.9 | 139.6 | 120.4 | 101.2 | 81.9 | - | 166.2 | 18.8 | 156.9 | 137.7 | 118.4 | 99.2 | 80.0 | - |
|
| 62 | 159.2 | 16.9 | 159.2 | 159.2 | 147.2 | 128.0 | 108.7 | 89.5 | 157.1 | 18.6 | 157.1 | 157.1 | 145.6 | 126.6 | 107.1 | 87.9 |
|
| 57 | 156.4 | 16.9 | 156.4 | 156.4 | 145.9 | 126.7 | 107.5 | 88.2 | 152.2 | 18.5 | 152.2 | 152.2 | 141.4 | 122.6 | 103.0 | 83.7 |
|
| 77 | 204.7 | 17.9 | 113.7 | 92.4 | 71.1 | - | - | - | 198.9 | 19.5 | 111.3 | 90.0 | 68.7 | - | - | - |
|
| 72 | 190.4 | 17.6 | 142.3 | 121.0 | 99.7 | 78.4 | - | - | 184.8 | 19.2 | 140.0 | 118.7 | 97.4 | 76.1 | - | - |
6000 |
| 67 | 176.1 | 17.2 | 170.9 | 149.6 | 128.3 | 107.0 | 85.7 | - | 170.6 | 18.9 | 168.7 | 147.4 | 126.1 | 104.9 | 83.6 | - |
|
| 62 | 163.9 | 17.0 | 163.9 | 163.9 | 156.8 | 135.5 | 114.2 | 92.9 | 161.3 | 18.7 | 161.3 | 161.3 | 155.1 | 134.3 | 112.5 | 91.2 |
|
| 57 | 161.0 | 17.0 | 161.0 | 161.0 | 155.4 | 134.2 | 112.9 | 91.6 | 156.2 | 18.6 | 156.2 | 156.2 | 150.7 | 130.2 | 108.1 | 86.8 |
|
| 72 | 192.4 | 17.6 | 149.4 | 126.5 | 103.6 | 80.8 | - | - | 187.0 | 19.3 | 147.1 | 124.3 | 101.4 | 78.6 | - | - |
6750 |
| 67 | 177.9 | 17.3 | 175.3 | 156.2 | 133.4 | 110.5 | 87.7 | - | 172.7 | 18.9 | 171.7 | 154.2 | 131.4 | 108.5 | 85.7 | - |
| 62 | 165.6 | 17.1 | 165.6 | 165.6 | 162.1 | 139.2 | 116.3 | 93.5 | 163.2 | 18.7 | 163.2 | 163.2 | 160.1 | 137.5 | 114.4 | 91.6 | |
|
| |||||||||||||||||
|
| 57 | 162.6 | 17.0 | 162.6 | 162.6 | 159.9 | 137.0 | 114.1 | 91.3 | 158.1 | 18.7 | 158.1 | 158.1 | 155.3 | 132.9 | 109.6 | 86.8 |
|
| 72 | 194.3 | 17.7 | 156.5 | 132.0 | 107.6 | 83.2 | - | - | 189.2 | 19.3 | 154.2 | 129.9 | 105.5 | 81.1 | - | - |
7500 |
| 67 | 179.7 | 17.4 | 179.7 | 162.9 | 138.5 | 114.1 | 89.6 | - | 174.7 | 19.0 | 174.7 | 161.0 | 136.6 | 112.2 | 87.8 | - |
| 62 | 167.3 | 17.1 | 167.3 | 167.3 | 167.3 | 142.9 | 118.4 | 94.0 | 165.1 | 18.8 | 165.1 | 165.1 | 165.1 | 140.7 | 116.3 | 92.0 | |
|
| |||||||||||||||||
|
| 57 | 164.3 | 17.1 | 164.3 | 164.3 | 164.3 | 139.8 | 115.4 | 91.0 | 159.9 | 18.7 | 159.9 | 159.9 | 159.9 | 135.6 | 111.2 | 86.8 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
32 | Johnson Controls Unitary Products |