Johnson Controls R-410A manual PH-15 / NH-15, PJ-15 / NJ-15, 68.2

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 59
Image 59
68.2

505430-BTG-A-0309

PH-15 / NH-15

Air Over Evaporator Coil

Capacity1 &

 

 

Outdoor Temperature (°F @ 72% RH)

 

 

CFM

DB (°F)

kW

-10

0

10

20

30

40

50

60

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

68.2

80.0

93.8

110.0

129.1

151.5

177.8

208.7

 

KW

11.8

12.2

12.7

13.2

13.7

14.1

14.6

15.1

 

 

4500

70

MBH

61.5

73.2

87.0

103.2

122.3

144.7

171.0

201.9

KW

13.5

14.0

14.4

14.9

15.4

15.9

16.3

16.8

 

 

 

80

MBH

57.6

69.3

83.1

99.3

118.4

140.8

167.1

198.0

 

KW

15.0

15.5

16.0

16.4

16.9

17.4

17.9

18.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

74.0

85.8

99.6

115.8

134.9

157.3

183.6

214.5

 

KW

11.2

11.7

12.2

12.6

13.1

13.6

14.1

14.6

 

 

6000

70

MBH

67.3

79.0

92.8

109.0

128.1

150.5

176.8

207.7

KW

12.9

13.4

13.9

14.4

14.8

15.3

15.8

16.3

 

 

 

80

MBH

63.4

75.1

88.9

105.1

124.2

146.6

172.9

203.8

 

KW

14.5

14.9

15.4

15.9

16.4

16.8

17.3

17.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

72.4

84.1

97.9

114.1

133.2

155.6

181.9

212.8

 

KW

12.0

12.5

13.0

13.4

13.9

14.4

14.9

15.4

 

 

7500

70

MBH

65.6

77.3

91.1

107.4

126.4

148.8

175.1

206.0

KW

13.7

14.2

14.7

15.2

15.6

16.1

16.6

17.1

 

 

 

80

MBH

61.7

73.4

87.3

103.5

122.5

144.9

171.2

202.1

 

KW

15.3

15.7

16.2

16.7

17.2

17.6

18.1

18.6

 

 

 

 

 

 

 

 

 

 

 

 

 

1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.

PJ-15 / NJ-15

Air Over Evaporator Coil

Capacity1 &

 

 

Outdoor Temperature (°F @ 72% RH)

 

 

CFM

DB (°F)

kW

-10

0

10

20

30

40

50

60

 

55

MBH

65.6

77.0

90.3

105.8

123.9

145.1

169.7

198.5

 

KW

10.0

10.5

11.1

11.6

12.2

12.7

13.3

13.8

 

 

4500

70

MBH

62.2

73.6

86.9

102.4

120.5

141.6

166.3

195.1

KW

12.0

12.5

13.1

13.6

14.2

14.7

15.3

15.8

 

 

 

80

MBH

59.5

70.9

84.1

99.7

117.8

138.9

163.6

192.4

 

KW

13.4

13.9

14.5

15.0

15.6

16.1

16.7

17.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

71.6

83.0

96.3

111.8

129.9

151.0

175.7

204.5

 

KW

9.6

10.2

10.7

11.3

11.8

12.4

12.9

13.4

 

 

6000

70

MBH

68.1

79.5

92.8

108.3

126.5

147.6

172.3

201.1

KW

11.6

12.2

12.7

13.3

13.8

14.3

14.9

15.4

 

 

 

80

MBH

65.4

76.8

90.1

105.6

123.7

144.9

169.6

198.3

 

KW

13.0

13.6

14.1

14.7

15.2

15.8

16.3

16.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

MBH

74.0

85.4

98.7

114.2

132.4

153.5

178.2

207.0

 

KW

11.3

11.8

12.4

12.9

13.5

14.0

14.6

15.1

 

 

7500

70

MBH

70.6

82.0

95.3

110.8

128.9

150.1

174.7

203.5

KW

13.3

13.8

14.4

14.9

15.5

16.0

16.6

17.1

 

 

 

80

MBH

67.9

79.3

92.6

108.1

126.2

147.4

172.0

200.8

 

KW

14.7

15.3

15.8

16.4

16.9

17.5

18.0

18.5

 

 

 

 

 

 

 

 

 

 

 

 

 

1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated motor efficiency.

Johnson Controls Unitary Products

59

Page 59
Image 59
Johnson Controls R-410A manual PH-15 / NH-15, PJ-15 / NJ-15, 68.2