Air Over Evaporator Coil | Capacity1 & |
|
| Outdoor Temperature (°F @ 72% RH) |
|
| |||||
CFM | DB (°F) | kW | 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 68.2 | 80.0 | 93.8 | 110.0 | 129.1 | 151.5 | 177.8 | 208.7 | |
| KW | 11.8 | 12.2 | 12.7 | 13.2 | 13.7 | 14.1 | 14.6 | 15.1 | ||
|
| ||||||||||
4500 | 70 | MBH | 61.5 | 73.2 | 87.0 | 103.2 | 122.3 | 144.7 | 171.0 | 201.9 | |
KW | 13.5 | 14.0 | 14.4 | 14.9 | 15.4 | 15.9 | 16.3 | 16.8 | |||
|
| ||||||||||
| 80 | MBH | 57.6 | 69.3 | 83.1 | 99.3 | 118.4 | 140.8 | 167.1 | 198.0 | |
| KW | 15.0 | 15.5 | 16.0 | 16.4 | 16.9 | 17.4 | 17.9 | 18.3 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 74.0 | 85.8 | 99.6 | 115.8 | 134.9 | 157.3 | 183.6 | 214.5 | |
| KW | 11.2 | 11.7 | 12.2 | 12.6 | 13.1 | 13.6 | 14.1 | 14.6 | ||
|
| ||||||||||
6000 | 70 | MBH | 67.3 | 79.0 | 92.8 | 109.0 | 128.1 | 150.5 | 176.8 | 207.7 | |
KW | 12.9 | 13.4 | 13.9 | 14.4 | 14.8 | 15.3 | 15.8 | 16.3 | |||
|
| ||||||||||
| 80 | MBH | 63.4 | 75.1 | 88.9 | 105.1 | 124.2 | 146.6 | 172.9 | 203.8 | |
| KW | 14.5 | 14.9 | 15.4 | 15.9 | 16.4 | 16.8 | 17.3 | 17.8 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 72.4 | 84.1 | 97.9 | 114.1 | 133.2 | 155.6 | 181.9 | 212.8 | |
| KW | 12.0 | 12.5 | 13.0 | 13.4 | 13.9 | 14.4 | 14.9 | 15.4 | ||
|
| ||||||||||
7500 | 70 | MBH | 65.6 | 77.3 | 91.1 | 107.4 | 126.4 | 148.8 | 175.1 | 206.0 | |
KW | 13.7 | 14.2 | 14.7 | 15.2 | 15.6 | 16.1 | 16.6 | 17.1 | |||
|
| ||||||||||
| 80 | MBH | 61.7 | 73.4 | 87.3 | 103.5 | 122.5 | 144.9 | 171.2 | 202.1 | |
| KW | 15.3 | 15.7 | 16.2 | 16.7 | 17.2 | 17.6 | 18.1 | 18.6 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
Air Over Evaporator Coil | Capacity1 & |
|
| Outdoor Temperature (°F @ 72% RH) |
|
| |||||
CFM | DB (°F) | kW | 0 | 10 | 20 | 30 | 40 | 50 | 60 | ||
| 55 | MBH | 65.6 | 77.0 | 90.3 | 105.8 | 123.9 | 145.1 | 169.7 | 198.5 | |
| KW | 10.0 | 10.5 | 11.1 | 11.6 | 12.2 | 12.7 | 13.3 | 13.8 | ||
|
| ||||||||||
4500 | 70 | MBH | 62.2 | 73.6 | 86.9 | 102.4 | 120.5 | 141.6 | 166.3 | 195.1 | |
KW | 12.0 | 12.5 | 13.1 | 13.6 | 14.2 | 14.7 | 15.3 | 15.8 | |||
|
| ||||||||||
| 80 | MBH | 59.5 | 70.9 | 84.1 | 99.7 | 117.8 | 138.9 | 163.6 | 192.4 | |
| KW | 13.4 | 13.9 | 14.5 | 15.0 | 15.6 | 16.1 | 16.7 | 17.2 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 71.6 | 83.0 | 96.3 | 111.8 | 129.9 | 151.0 | 175.7 | 204.5 | |
| KW | 9.6 | 10.2 | 10.7 | 11.3 | 11.8 | 12.4 | 12.9 | 13.4 | ||
|
| ||||||||||
6000 | 70 | MBH | 68.1 | 79.5 | 92.8 | 108.3 | 126.5 | 147.6 | 172.3 | 201.1 | |
KW | 11.6 | 12.2 | 12.7 | 13.3 | 13.8 | 14.3 | 14.9 | 15.4 | |||
|
| ||||||||||
| 80 | MBH | 65.4 | 76.8 | 90.1 | 105.6 | 123.7 | 144.9 | 169.6 | 198.3 | |
| KW | 13.0 | 13.6 | 14.1 | 14.7 | 15.2 | 15.8 | 16.3 | 16.9 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| |
| 55 | MBH | 74.0 | 85.4 | 98.7 | 114.2 | 132.4 | 153.5 | 178.2 | 207.0 | |
| KW | 11.3 | 11.8 | 12.4 | 12.9 | 13.5 | 14.0 | 14.6 | 15.1 | ||
|
| ||||||||||
7500 | 70 | MBH | 70.6 | 82.0 | 95.3 | 110.8 | 128.9 | 150.1 | 174.7 | 203.5 | |
KW | 13.3 | 13.8 | 14.4 | 14.9 | 15.5 | 16.0 | 16.6 | 17.1 | |||
|
| ||||||||||
| 80 | MBH | 67.9 | 79.3 | 92.6 | 108.1 | 126.2 | 147.4 | 172.0 | 200.8 | |
| KW | 14.7 | 15.3 | 15.8 | 16.4 | 16.9 | 17.5 | 18.0 | 18.5 | ||
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
1These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
Johnson Controls Unitary Products | 59 |