YH-20 / NH-20 (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 244.4 | 23.4 | 120.7 | 96.0 | 71.4 | - | - | - | 229.9 | 25.9 | 117.5 | 92.5 | 67.5 | - | - | - |
|
| 72 | 226.2 | 22.8 | 156.5 | 131.9 | 107.2 | 82.6 | - | - | 212.8 | 25.1 | 153.2 | 128.2 | 103.2 | 78.1 | - | - |
6000 |
| 67 | 208.0 | 22.1 | 192.4 | 167.7 | 143.1 | 118.5 | 93.8 | - | 195.7 | 24.3 | 188.9 | 163.9 | 138.9 | 113.8 | 88.8 | - |
|
| 62 | 192.2 | 21.6 | 192.2 | 192.2 | 178.1 | 153.5 | 128.8 | 104.2 | 179.4 | 23.8 | 179.4 | 179.4 | 173.7 | 148.6 | 123.6 | 98.6 |
|
| 57 | 194.4 | 21.8 | 194.4 | 194.4 | 174.8 | 150.2 | 125.5 | 100.9 | 184.6 | 23.9 | 184.6 | 184.6 | 162.9 | 137.9 | 112.9 | 87.8 |
|
| 77 | 250.0 | 23.5 | 136.5 | 104.5 | 76.9 | - | - | - | 235.5 | 25.9 | 135.8 | 101.0 | 72.8 | - | - | - |
|
| 72 | 231.4 | 22.8 | 170.8 | 143.1 | 115.5 | 87.9 | - | - | 218.0 | 25.1 | 167.7 | 139.5 | 111.3 | 83.1 | - | - |
7000 |
| 67 | 212.8 | 22.1 | 205.0 | 181.7 | 154.1 | 126.5 | 98.9 | - | 200.5 | 24.3 | 199.6 | 178.0 | 149.8 | 121.6 | 93.4 | - |
|
| 62 | 196.7 | 21.7 | 196.7 | 196.7 | 191.8 | 164.2 | 136.5 | 108.9 | 183.8 | 23.8 | 183.8 | 183.8 | 183.8 | 159.9 | 130.9 | 102.7 |
|
| 57 | 198.9 | 21.8 | 198.9 | 198.9 | 188.3 | 160.6 | 133.0 | 105.4 | 189.1 | 24.0 | 189.1 | 189.1 | 175.8 | 148.8 | 119.4 | 91.2 |
|
| 77 | 255.7 | 23.5 | 152.4 | 113.0 | 82.4 | - | - | - | 241.1 | 25.9 | 154.0 | 109.5 | 78.1 | - | - | - |
|
| 72 | 236.6 | 22.8 | 185.0 | 154.4 | 123.7 | 93.1 | - | - | 223.2 | 25.1 | 182.1 | 150.8 | 119.4 | 88.0 | - | - |
8000 |
| 67 | 217.6 | 22.2 | 217.6 | 195.7 | 165.1 | 134.5 | 103.9 | - | 205.3 | 24.3 | 205.3 | 192.1 | 160.7 | 129.3 | 97.9 | - |
|
| 62 | 201.1 | 21.7 | 201.1 | 201.1 | 205.5 | 174.9 | 144.3 | 113.6 | 188.2 | 23.9 | 188.2 | 188.2 | 188.2 | 171.2 | 138.2 | 106.9 |
|
| 57 | 203.3 | 21.8 | 203.3 | 203.3 | 201.7 | 171.1 | 140.5 | 109.8 | 193.6 | 24.0 | 193.6 | 193.6 | 188.6 | 159.7 | 125.9 | 94.5 |
|
| 72 | 241.9 | 23.0 | 195.9 | 162.8 | 129.7 | 96.5 | - | - | 228.6 | 25.4 | 193.3 | 159.5 | 125.8 | 92.0 | - | - |
9000 |
| 67 | 222.4 | 22.3 | 222.4 | 206.1 | 173.0 | 139.9 | 106.8 | - | 210.3 | 24.6 | 210.3 | 203.0 | 169.3 | 135.5 | 101.7 | - |
| 62 | 205.6 | 21.9 | 205.6 | 205.6 | 207.8 | 174.6 | 141.5 | 108.4 | 192.7 | 24.1 | 192.7 | 192.7 | 192.7 | 167.4 | 132.8 | 99.0 | |
|
| |||||||||||||||||
|
| 57 | 207.9 | 22.0 | 207.9 | 207.9 | 207.0 | 173.9 | 140.8 | 107.7 | 198.3 | 24.2 | 198.3 | 198.3 | 195.8 | 163.2 | 128.2 | 94.4 |
|
| 72 | 247.2 | 23.2 | 206.8 | 171.2 | 135.6 | 100.0 | - | - | 233.9 | 25.6 | 204.5 | 168.3 | 132.1 | 95.9 | - | - |
10000 |
| 67 | 227.3 | 22.5 | 227.3 | 216.5 | 180.9 | 145.3 | 109.7 | - | 215.2 | 24.8 | 215.2 | 214.0 | 177.8 | 141.6 | 105.4 | - |
| 62 | 210.0 | 22.0 | 210.0 | 210.0 | 210.0 | 174.4 | 138.8 | 103.2 | 197.3 | 24.3 | 197.3 | 197.3 | 197.3 | 163.5 | 127.4 | 91.2 | |
|
| |||||||||||||||||
|
| 57 | 212.4 | 22.2 | 212.4 | 212.4 | 212.4 | 176.8 | 141.2 | 105.6 | 202.9 | 24.5 | 202.9 | 202.9 | 202.9 | 166.7 | 130.5 | 94.3 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
40 | Johnson Controls Unitary Products |