Johnson Controls R-410A Airflow Performance, Example Supply Air Blower Performance, RPM Selection

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 69
Image 69
Drive Selection

505430-BTG-A-0309

Drive Selection

1.Determine Upflow or Horizontal supply duct Application.

2.Determine desired airflow.

3.Calculate or measure the amount of external static pressure.

4.Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)

5.Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.

6.Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.

7.Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.

8.Determine turns open to obtain the desired operation point.

Example

1.3250 CFM

2.1.4 iwg

3.Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.

4.Using the RPM selection table below, Model X is found.

5.1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.

6.1100 RPM is within the range of the 2 HP drives.

7.Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.

Airflow Performance

Example Supply Air Blower Performance

 

 

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG

 

 

 

 

 

 

 

 

 

 

(CFM)

0.2

0.4

0.6

 

0.8

 

1.0

1.2

1.4

 

 

1.6

 

 

1.8

2.0

 

RPM

BHP

RPM

BHP

RPM

 

BHP

 

RPM

 

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

Standard 1.5 HP & Drive

 

 

 

 

 

 

High Static 2 HP & Drive

 

 

3000

 

 

 

 

822

 

1.2

 

891

 

1.3

 

 

 

 

 

1077

 

1.6

 

1135

 

1.8

 

 

 

 

 

696

0.9

757

1.1

 

 

 

 

961

1.3

1019

1.5

 

 

 

 

 

 

 

 

3250

729

1.1

790

1.3

855

 

1.4

 

924

 

1.5

 

984

1.6

1042

1.7

1100

 

1.8

 

1159

 

2.0

 

 

 

 

 

3500

766

1.3

826

1.5

892

 

1.6

 

953

 

1.6

 

1010

1.8

1069

1.9

1127

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM Selection

Unit Model

 

HP

Max

Motor

Blower

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1 Turn

Fully

 

BHP

Sheave

Sheave

Open

Open

Open

Open

Open

Open

Closed

 

 

 

X

Std.

1.5

1.73

1VL40

AK69

N/A

690

743

796

849

902

955

HS

2

2.30

1VL40

AK56

N/A

863

929

995

1062

1128

1194

 

Johnson Controls Unitary Products

69

Page 69
Image 69
Johnson Controls R-410A manual Airflow Performance, Example Supply Air Blower Performance, Drive Selection, RPM Selection