Drive Selection
1.Determine Upflow or Horizontal supply duct Application.
2.Determine desired airflow.
3.Calculate or measure the amount of external static pressure.
4.Using the operating point, determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance table. (Linear interpolation may be necessary.)
5.Noting the RPM and BHP from step 4, locate the appropriate motor and/or drive on the RPM selection table.
6.Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the chosen motor.
8.Determine turns open to obtain the desired operation point.
Example
1.3250 CFM
2.1.4 iwg
3.Using the supply air blower performance table below, the following data point was located: 1100 RPM & 1.8 BHP.
4.Using the RPM selection table below, Model X is found.
5.1.8 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.1100 RPM is within the range of the 2 HP drives.
7.Using the 2 HP motor and drive, 1 turn open will achieve 1128 RPM.
Airflow Performance
Example Supply Air Blower Performance
|
|
|
|
|
|
|
|
|
| Available External Static Pressure - IWG |
|
|
|
|
|
|
|
|
|
| ||||||||
(CFM) | 0.2 | 0.4 | 0.6 |
| 0.8 |
| 1.0 | 1.2 | 1.4 |
|
| 1.6 |
|
| 1.8 | 2.0 | ||||||||||||
| RPM | BHP | RPM | BHP | RPM |
| BHP |
| RPM |
| BHP | RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | ||||
|
|
|
|
|
|
|
|
| Standard 1.5 HP & Drive |
|
|
|
|
|
| High Static 2 HP & Drive |
|
| ||||||||||
3000 |
|
|
|
| 822 |
| 1.2 |
| 891 |
| 1.3 |
|
|
|
|
| 1077 |
| 1.6 |
| 1135 |
| 1.8 |
|
|
|
|
|
696 | 0.9 | 757 | 1.1 |
|
|
|
| 961 | 1.3 | 1019 | 1.5 |
|
|
|
|
|
|
|
| |||||||||
3250 | 729 | 1.1 | 790 | 1.3 | 855 |
| 1.4 |
| 924 |
| 1.5 |
| 984 | 1.6 | 1042 | 1.7 | 1100 |
| 1.8 |
| 1159 |
| 2.0 |
|
|
|
|
|
3500 | 766 | 1.3 | 826 | 1.5 | 892 |
| 1.6 |
| 953 |
| 1.6 |
| 1010 | 1.8 | 1069 | 1.9 | 1127 |
| 2.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RPM Selection
Unit Model |
| HP | Max | Motor | Blower | 6 Turns | 5 Turns | 4 Turns | 3 Turns | 2 Turns | 1 Turn | Fully | |
| BHP | Sheave | Sheave | Open | Open | Open | Open | Open | Open | Closed | |||
|
|
| |||||||||||
X | Std. | 1.5 | 1.73 | 1VL40 | AK69 | N/A | 690 | 743 | 796 | 849 | 902 | 955 | |
HS | 2 | 2.30 | 1VL40 | AK56 | N/A | 863 | 929 | 995 | 1062 | 1128 | 1194 | ||
|
Johnson Controls Unitary Products | 69 |