505430-BTG-A-0309

YJ-15 / Two NH-07

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

90

85

80

75

70

65

(MBh)

(kW)2

90

85

80

75

70

65

 

 

 

 

 

 

75°F

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

77

216.0

12.0

105.9

88.7

71.5

-

-

-

208.8

13.2

103.4

86.2

69.0

-

-

-

 

 

72

200.4

11.7

130.4

113.2

96.0

78.8

-

-

194.2

12.9

128.0

110.9

93.7

76.5

-

-

4500

 

67

184.8

11.4

154.8

137.7

120.5

103.3

86.1

-

179.6

12.6

152.7

135.5

118.3

101.2

84.0

-

 

 

62

173.1

11.2

173.1

164.2

147.0

129.8

112.6

95.4

165.4

12.4

165.4

161.0

143.8

126.6

109.4

92.3

 

 

57

165.6

11.1

165.6

165.6

150.2

133.0

115.8

98.6

162.3

12.3

162.3

162.3

147.5

130.3

113.1

95.9

 

 

77

222.3

12.1

114.8

95.5

76.2

-

-

-

215.7

13.2

112.2

93.0

73.7

-

-

-

 

 

72

206.2

11.8

140.8

121.5

102.3

83.0

-

-

200.5

13.0

138.5

119.3

100.0

80.8

-

-

5250

 

67

190.2

11.5

166.9

147.6

128.3

109.0

89.8

-

185.4

12.7

164.9

145.6

126.3

107.1

87.8

-

 

 

62

178.1

11.2

178.1

173.7

156.5

137.8

118.0

98.7

170.8

12.4

170.8

168.6

153.5

134.2

115.0

95.7

 

 

57

170.4

11.2

170.4

170.4

159.9

141.5

121.4

102.1

167.6

12.4

167.6

167.6

157.4

138.2

118.9

99.6

 

 

77

228.6

12.1

123.6

102.2

80.9

-

-

-

222.5

13.3

121.1

99.7

78.4

-

-

-

 

 

72

212.1

11.9

151.3

129.9

108.5

87.1

-

-

206.9

13.1

149.0

127.7

106.4

85.0

-

-

6000

 

67

195.6

11.6

178.9

157.6

136.2

114.8

93.4

-

191.3

12.8

177.0

155.7

134.3

113.0

91.6

-

 

 

62

183.2

11.3

183.2

183.2

166.1

145.8

123.4

102.0

176.2

12.5

176.2

176.2

163.2

141.9

120.5

99.2

 

 

57

175.2

11.3

175.2

175.2

169.7

149.9

127.0

105.6

172.9

12.5

172.9

172.9

167.4

146.0

124.7

103.3

 

 

72

216.4

11.9

159.1

136.1

113.1

90.1

-

-

209.8

13.1

156.5

133.5

110.6

87.6

-

-

6750

 

67

199.6

11.6

188.8

164.9

141.9

118.9

95.9

-

193.9

12.8

185.6

162.6

139.7

116.7

93.7

-

 

62

186.9

11.4

186.9

186.9

173.4

150.9

127.4

104.4

178.7

12.6

178.7

178.7

169.7

146.7

123.8

100.8

 

 

 

 

57

178.8

11.3

178.8

178.8

176.1

153.9

130.1

107.1

175.3

12.5

175.3

175.3

172.5

149.6

126.6

103.7

 

 

72

220.7

12.0

166.9

142.3

117.7

93.0

-

-

212.6

13.2

163.9

139.3

114.8

90.2

-

-

7500

 

67

203.5

11.7

198.6

172.3

147.7

123.0

98.4

-

196.6

12.9

194.1

169.5

145.0

120.4

95.8

-

 

62

190.6

11.4

190.6

190.6

180.6

156.0

131.4

106.8

181.1

12.6

181.1

181.1

176.1

151.6

127.0

102.4

 

 

 

 

57

182.4

11.4

182.4

182.4

182.4

157.8

133.2

108.6

177.7

12.6

177.7

177.7

177.7

153.1

128.5

104.0

 

 

 

 

 

 

95°F

 

 

 

 

 

 

 

105°F

 

 

 

 

 

 

77

201.7

14.3

100.9

83.7

66.6

-

-

-

197.4

16.0

98.8

81.6

64.5

-

-

-

 

 

72

188.0

14.1

125.7

108.5

91.4

74.2

-

-

183.8

15.7

123.8

106.6

89.4

72.3

-

-

4500

 

67

174.3

13.8

150.5

133.4

116.2

99.1

81.9

-

170.2

15.4

148.7

131.6

114.4

97.2

80.0

-

 

 

62

157.8

13.5

157.8

157.8

140.6

123.4

106.3

89.1

156.2

15.2

156.2

156.2

139.1

121.9

104.8

87.6

 

 

57

159.0

13.5

159.0

159.0

144.7

127.6

110.4

93.3

155.4

15.2

155.4

155.4

140.6

123.4

106.2

89.1

 

 

77

209.0

14.4

109.7

90.5

71.2

-

-

-

204.0

16.1

107.4

88.2

69.0

-

-

-

 

 

72

194.9

14.2

136.3

117.0

97.8

78.6

-

-

189.9

15.8

134.1

114.9

95.7

76.4

-

-

5250

 

67

180.7

13.9

162.8

143.6

124.4

105.1

85.9

-

175.8

15.5

160.9

141.6

122.4

103.1

83.9

-

 

 

62

163.5

13.6

163.5

163.5

150.5

130.7

112.0

92.7

161.4

15.3

161.4

161.4

148.8

129.3

110.4

91.1

 

 

57

164.8

13.6

164.8

164.8

154.9

134.8

116.4

97.2

160.6

15.3

160.6

160.6

150.4

130.8

111.9

92.7

 

 

77

216.4

14.5

118.5

97.2

75.9

-

-

-

210.6

16.2

116.1

94.8

73.5

-

-

-

 

 

72

201.7

14.2

146.8

125.5

104.2

82.9

-

-

196.1

15.9

144.5

123.2

101.9

80.6

-

-

6000

 

67

187.0

14.0

175.1

153.8

132.5

111.2

89.9

-

181.5

15.6

173.0

151.7

130.4

109.1

87.8

-

 

 

62

169.3

13.7

169.3

169.3

160.3

137.9

117.7

96.4

166.6

15.4

166.6

166.6

158.6

136.7

116.0

94.7

 

 

57

170.5

13.7

170.5

170.5

165.0

142.1

122.4

101.1

165.8

15.3

165.8

165.8

160.2

138.1

117.6

96.3

 

 

72

203.1

14.3

153.9

131.0

108.0

85.1

-

-

197.7

15.9

151.6

128.7

105.8

83.0

-

-

6750

 

67

188.3

14.0

182.4

160.3

137.4

114.5

91.6

-

183.1

15.7

178.8

158.3

135.4

112.5

89.6

-

 

62

170.5

13.8

170.5

170.5

166.0

142.5

120.2

97.2

168.0

15.4

168.0

168.0

164.0

140.9

118.2

95.4

 

 

 

 

57

171.7

13.7

171.7

171.7

169.0

145.3

123.2

100.2

167.2

15.4

167.2

167.2

164.4

141.1

118.7

95.8

 

 

72

204.5

14.3

160.9

136.4

111.9

87.4

-

-

199.4

16.0

158.7

134.2

109.8

85.3

-

-

7500

 

67

189.6

14.1

189.6

166.8

142.3

117.8

93.2

-

184.7

15.7

184.7

164.9

140.4

115.9

91.4

-

 

62

171.7

13.8

171.7

171.7

171.7

147.1

122.6

98.1

169.5

15.5

169.5

169.5

169.5

145.0

120.5

96.1

 

 

 

 

57

173.0

13.8

173.0

173.0

173.0

148.4

123.9

99.4

168.6

15.4

168.6

168.6

168.6

144.1

119.7

95.2

Johnson Controls Unitary Products

31

Page 31
Image 31
Johnson Controls R-410A manual YJ-15 / Two NH-07

R-410A specifications

Johnson Controls R-410A is a widely recognized refrigerant in the HVAC industry, primarily used in air conditioning and heat pump applications. Known for its environmental benefits and efficiency, R-410A has risen to prominence as a reliable replacement for older refrigerants such as R-22, which are being phased out due to their harmful impact on the ozone layer.

One of the standout features of R-410A is its low impact on global warming potential, making it an environmentally-friendly choice. It is composed of a mixture of hydrofluorocarbons (HFCs), specifically difluoromethane (R-32) and pentafluoroethane (R-125). This blend allows for efficient heat transfer while minimizing harmful emissions, addressing the growing concerns over climate change.

Johnson Controls emphasizes the efficiency of R-410A systems, which can provide a highly effective cooling performance. They are designed to operate at higher pressures compared to R-22, allowing for more efficient heat exchange and better overall system performance. This results in greater energy efficiency ratings, contributing to lower electricity bills for consumers.

In terms of technology, R-410A systems often feature advanced compressor designs and enhanced coil configurations, which optimize the system’s performance. Johnson Controls integrates state-of-the-art variable speed technologies and smart controls that enhance responsiveness and adaptability to changing environmental conditions. These innovations not only improve thermal comfort but also reduce energy consumption, leading to a smaller carbon footprint.

Another significant characteristic of R-410A is its compatibility with various lubricants, which is crucial for maintaining system performance and longevity. Johnson Controls often utilizes specially formulated lubricants that work optimally with R-410A, ensuring reliable operation and reducing the risk of issues related to lubrication.

In summary, Johnson Controls R-410A is an important refrigerant characterized by its efficient, environmentally friendly properties and advanced technologies. Its application in modern HVAC systems provides users with excellent performance, substantial energy savings, and an effective solution for climate-conscious cooling. As the industry continues to evolve, R-410A remains a central player in the push toward more sustainable and efficient heating and cooling solutions.