![PH-15 / NH-15 (Continued)](/images/new-backgrounds/35800/35800101x1.webp)
PH-15 / NH-15 (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 175.1 | 18.3 | 92.4 | 73.5 | 54.6 | - | - | - | 157.4 | 19.9 | 85.8 | 67.0 | 48.1 | - | - | - |
|
| 72 | 162.0 | 18.1 | 120.0 | 101.1 | 82.2 | 63.3 | - | - | 146.7 | 19.8 | 114.3 | 95.5 | 76.6 | 57.8 | - | - |
4500 |
| 67 | 148.8 | 18.0 | 147.6 | 128.7 | 109.8 | 91.0 | 72.1 | - | 136.1 | 19.6 | 136.1 | 124.0 | 105.1 | 86.3 | 67.4 | - |
|
| 62 | 138.1 | 17.8 | 138.1 | 138.1 | 134.4 | 115.5 | 96.6 | 77.7 | 126.2 | 19.5 | 126.2 | 126.2 | 126.2 | 107.5 | 88.6 | 69.7 |
|
| 57 | 143.6 | 17.8 | 143.6 | 143.6 | 126.1 | 107.2 | 88.3 | 69.4 | 132.1 | 19.6 | 132.1 | 132.1 | 114.2 | 95.4 | 76.5 | 57.6 |
|
| 77 | 179.2 | 18.3 | 112.3 | 80.6 | 58.9 | - | - | - | 161.8 | 19.9 | 110.6 | 74.3 | 52.6 | - | - | - |
|
| 72 | 165.7 | 18.1 | 132.0 | 110.4 | 88.7 | 67.1 | - | - | 150.8 | 19.8 | 126.9 | 105.3 | 83.6 | 62.0 | - | - |
5250 |
| 67 | 152.3 | 18.0 | 151.7 | 140.2 | 118.6 | 96.9 | 75.3 | - | 139.9 | 19.6 | 139.9 | 136.3 | 114.7 | 93.0 | 71.4 | - |
|
| 62 | 141.3 | 17.8 | 141.3 | 141.3 | 145.0 | 123.4 | 101.7 | 80.1 | 129.7 | 19.5 | 129.7 | 129.7 | 129.7 | 116.6 | 94.6 | 72.9 |
|
| 57 | 146.9 | 17.8 | 146.9 | 146.9 | 136.1 | 114.4 | 92.8 | 71.1 | 135.7 | 19.6 | 135.7 | 135.7 | 124.8 | 103.6 | 81.5 | 59.9 |
|
| 77 | 183.2 | 18.3 | 132.3 | 87.6 | 63.3 | - | - | - | 166.2 | 19.9 | 135.3 | 81.5 | 57.1 | - | - | - |
|
| 72 | 169.5 | 18.1 | 144.0 | 119.6 | 95.3 | 70.9 | - | - | 154.9 | 19.8 | 139.5 | 115.1 | 90.6 | 66.2 | - | - |
6000 |
| 67 | 155.8 | 18.0 | 155.8 | 151.6 | 127.3 | 102.9 | 78.5 | - | 143.6 | 19.6 | 143.6 | 143.6 | 124.2 | 99.8 | 75.4 | - |
|
| 62 | 144.5 | 17.8 | 144.5 | 144.5 | 155.7 | 131.3 | 106.9 | 82.5 | 133.2 | 19.5 | 133.2 | 133.2 | 133.2 | 125.8 | 100.5 | 76.1 |
|
| 57 | 150.2 | 17.9 | 150.2 | 150.2 | 146.0 | 121.6 | 97.3 | 72.9 | 139.4 | 19.6 | 139.4 | 139.4 | 135.3 | 111.9 | 86.5 | 62.1 |
|
| 72 | 171.9 | 18.2 | 155.2 | 128.6 | 102.0 | 75.4 | - | - | 156.4 | 19.8 | 149.5 | 122.9 | 96.3 | 69.7 | - | - |
6750 |
| 67 | 158.0 | 18.0 | 158.0 | 155.9 | 136.3 | 109.7 | 83.1 | - | 145.1 | 19.7 | 145.1 | 145.1 | 132.0 | 105.4 | 78.8 | - |
| 62 | 146.6 | 17.8 | 146.6 | 146.6 | 152.1 | 125.6 | 99.0 | 72.4 | 134.5 | 19.5 | 134.5 | 134.5 | 134.5 | 116.4 | 89.4 | 62.7 | |
|
| |||||||||||||||||
|
| 57 | 152.4 | 17.9 | 152.4 | 152.4 | 150.3 | 123.7 | 97.1 | 70.5 | 140.8 | 19.6 | 140.8 | 140.8 | 138.8 | 112.7 | 85.5 | 58.9 |
|
| 72 | 174.3 | 18.2 | 166.3 | 137.5 | 108.8 | 80.0 | - | - | 158.0 | 19.9 | 158.0 | 130.8 | 102.0 | 73.2 | - | - |
7500 |
| 67 | 160.2 | 18.1 | 160.2 | 160.2 | 145.3 | 116.5 | 87.7 | - | 146.5 | 19.8 | 146.5 | 146.5 | 139.9 | 111.1 | 82.3 | - |
| 62 | 148.6 | 17.9 | 148.6 | 148.6 | 148.6 | 119.8 | 91.0 | 62.3 | 135.8 | 19.6 | 135.8 | 135.8 | 135.8 | 107.0 | 78.2 | 49.4 | |
|
| |||||||||||||||||
|
| 57 | 154.5 | 18.0 | 154.5 | 154.5 | 154.5 | 125.7 | 96.9 | 68.1 | 142.2 | 19.7 | 142.2 | 142.2 | 142.2 | 113.4 | 84.6 | 55.8 |
1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ⎟ nameplate rated motor efficiency.
2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor
Johnson Controls Unitary Products | 51 |