Johnson Controls R-410A manual 208/230-3-60

Models: R-410A

1 100
Download 100 pages 63.88 Kb
Page 72
Image 72
Manual background

505430-BTG-A-0309

Electrical Data - Outdoor Unit - AC With Powered Convenience Outlet

 

 

Compressors

 

 

Outdoor Fan Motor

Pwr Conv

Minimum

Maximum

 

 

 

 

Outlet

Model

 

 

 

 

 

 

 

 

Circuit

Fuse Size

 

Power

Qty.

RLA

MCC

LRA

Qty

FLA

FLA

Ampacity1

(A)2

 

Supply

 

(each)

(each)

(each)

 

(each)

 

 

 

 

208/230-3-60

1

25.0

39

164

2

2.1

10.0

45.5

60

 

 

 

 

 

 

 

 

 

 

 

YH-07

460-3-60

1

12.2

19

100

2

1.2

5.0

22.6

30

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

1

9.0

14

78

2

0.9

4.0

17.1

25

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

15.6

24

110

2

3.0

10.0

51.2

60

 

 

 

 

 

 

 

 

 

 

 

YH-10

460-3-60

2

7.8

12

52

2

1.6

5.0

25.8

30

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

5.8

9

39

2

1.4

4.0

19.8

25

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

17.3

27

123

2

3.0

10.0

55.0

70

 

 

 

 

 

 

 

 

 

 

 

YJ-10

460-3-60

2

9.6

15

70

2

1.6

5.0

29.8

35

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

7.7

12

53

2

1.4

4.0

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

22.4

35

149

2

3.0

10.0

66.5

80

 

 

 

 

 

 

 

 

 

 

 

YH-12

460-3-60

2

10.6

17

75

2

1.6

5.0

32.1

40

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

7.7

12

54

2

1.4

4.0

24.0

30

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

23.1

36

160

2

3.0

10.0

68.0

90

 

 

 

 

 

 

 

 

 

 

 

YJ-12

460-3-60

2

12.2

19

87

2

1.6

5.0

35.7

45

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

8.7

14

62

2

1.4

4.0

26.3

30

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

YH-15

460-3-60

2

12.2

19

100

4

1.2

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

25.0

39

164

4

2.1

10.0

74.7

90

 

 

 

 

 

 

 

 

 

 

 

YJ-15

460-3-60

2

12.2

19

100

4

1.2

5.0

37.2

45

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

9.0

14

78

4

0.9

4.0

28.0

35

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

YH-20

460-3-60

2

16.7

26

114

4

1.6

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

2

30.1

47

225

4

3.0

10.0

89.8

110

 

 

 

 

 

 

 

 

 

 

 

YJ-20

460-3-60

2

16.7

26

114

4

1.6

5.0

49.0

60

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

2

12.2

19

80

4

1.4

4.0

36.9

45

 

 

 

 

 

 

 

 

 

 

 

1Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.

2Maximum fuse or maximum circuit breaker (HACR type per NEC).

Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.

72

Johnson Controls Unitary Products

Page 72
Image 72
Johnson Controls R-410A manual 208/230-3-60