Kohler 24VDC, 6VSG, 36VDC, 48VDC manual 5 Controller Fault Messages

Models: 48VDC 36VDC 24VDC 6VSG

1 60
Download 60 pages 54.87 Kb
Page 21
Image 21
Figure 2-5Controller Fault Messages

 

Warning (W) or

 

 

Fault Message

Shutdown(SD)

Condition

Check

 

 

 

 

Enclosure

W

The enclosure door is open. (Optional

Check for evidence of unauthorized

Intrusion Alarm

 

communications kit required.)

access to the generator set. Close

 

 

 

and lock the enclosure door.

 

 

 

 

Engine Oil

SD *

The LOP switch indicates low oil pressure for

Check for leaks in the lubrication

Pressure Low

 

more than 5 seconds. Function becomes active

system.

 

 

30 seconds after crank disconnect (30 second

Check the oil level and add oil if the

 

 

inhibit). Note: The low oil pressure shutdown

 

 

level is low.

 

 

does not protect against low oil level. Check the

 

 

 

 

 

engine oil level regularly as recommended in

 

 

 

Section 4.

 

 

 

 

 

Fuel Pressure

W

The fuel pressure switch measures low fuel

Check fuel supply and fuel lines.

Low

 

pressure (below 4.5 inches water column).

 

 

 

(Optional communications kit required.)

 

 

 

 

 

Engine Speed

SD *

Engine speed exceeds 115% of the normal

Contact an authorized

High

 

running speed for more than 0.3 seconds.

distributor/dealer for service.

 

 

 

 

Exer Not Sch

W

Exercise not scheduled. No exercise is

See Section 3.6 for instructions to set

 

 

scheduled on the controller.

the exerciser.

 

 

 

 

Generator

SD *

Generator voltage high. Output voltage exceeds

Contact an authorized

VoltageL1-L2

 

120% of the system nominal voltage for more

distributor/dealer for service.

High

 

than 2 seconds.

 

 

 

 

 

Lo Crank Vlt

W

Low cranking voltage. Battery voltage falls below

Charge or replace the battery.

 

 

8 VDC for more than 6 seconds while the starter

 

 

 

is engaged.

 

 

 

 

 

Locked Rotor

SD

No engine rotation is sensed during cranking.

Check the battery.

 

 

Shuts down 3 seconds after the fault is detected.

Check for loose connections.

 

 

 

 

 

 

Contact an authorized

 

 

 

distributor/dealer for service.

 

 

 

 

MainPwrOverL

SD

Main power overload. An over current fault on the

Contact an authorized

Shutdown

 

controller output (short circuit).

distributor/dealer for service.

 

 

 

 

Not in Auto

W

The generator set is not in Automatic (standby)

Press AUTO to place the generator

 

 

mode. Remote start and stop commands from a

set in Automatic mode, when

 

 

transfer switch or remote switch will be ignored.

appropriate.

 

 

 

 

Over Crank

SD

Three unsuccessful starting attempts.

Check the fuel supply, spark plug, and

 

 

 

battery.

 

 

 

Check for loose connections.

 

 

 

Contact an authorized

 

 

 

distributor/dealer for service.

 

 

 

 

Reserve Oil

W

The oil makeup kit reservoir bottle is empty.

Add oil to the oil makeup kit reservoir.

Empty

 

(Optional communications kit and oil makeup kit

 

 

 

required.)

 

 

 

 

 

Speed Sensor

SD

Engine speed sensing has failed or engine

Contact an authorized

Fault

 

stalled.

distributor/dealer for service.

 

 

 

 

* Engine cooldown runs before shutting down.

Figure 2-5Controller Fault Messages

TP-6843 1/13

Section 2 Generator Set Operation 21

Page 21
Image 21
Kohler 24VDC, 6VSG, 36VDC, 48VDC manual 5 Controller Fault Messages