2.6.3Resetting the Controller After a Fault Shutdown

Always identify and correct the cause of a fault shutdown before resetting the controller. Check the fault message displayed on the controller and refer to Figure 2-5to identify and correct the fault condition

before proceeding. Contact an authorized distributor/dealer for service, if necessary.

Press the OFF button to reset the controller, or follow the procedure below. See Figure 2-4.

1.While the fault message is displayed, press the Select button to go to the Overview menu.

2.Press Select again. The active fault message is displayed.

3.Press Select. Confirm Clear Fault: NO is displayed.

4.Press the UP arrow button. Confirm Clear Fault: YES is displayed.

5.Press the Select button to enter YES and clear the fault.

6.Press the Select button to return to the overview menu. The controller changes to OFF mode.

7.Press AUTO to put the generator set into automatic mode.

Fault Message

Overview ---->

Fault Message

Confirm Clear

 

1.2 h

 

Fault: NO

 

 

 

Press UP

 

 

 

arrow button.

 

 

 

Confirm Clear

 

 

 

Fault: YES

 

 

 

tp6809

Figure 2-4Clearing a Fault on the VSC Controller

 

Warning (W) or

 

 

Fault Message

Shutdown(SD)

Condition

Check

 

 

 

 

Accy PwrOver

W

Accessory Power Overload. Too many devices

Contact an authorized

Warning

 

on the accessory power port or an over current

distributor/dealer for service.

 

 

fault (short circuit) on the accessory controller

 

 

 

power output. (Feeds RBUS devices - PIM)

 

 

 

 

 

Aux Input

SD *

Auxiliary input. An optional customer-connected

Check customer-supplied equipment.

 

 

input is closed. (Digital input from optional PIM.)

 

 

 

 

 

Batt Chg Flt

W

Battery charger fault. Input to PIM from an

Check external battery charger.

 

 

external battery charger (not the built-in battery

 

 

 

charger).

 

 

 

 

 

Battery Voltage

W

Engine starting battery voltage is critically low,

Check the battery rating and

CrLow

 

less than 10.5 VDC.

condition.

 

 

 

Check the battery charger operation.

 

 

 

Charge or replace the battery.

 

 

 

 

Battery Voltage

W

Engine starting battery voltage rises above

Check the battery rating and

High

 

16 VDC for more than 10 seconds. Inhibited

condition.

 

 

during the engine crank cycle.

Check the battery charger operation.

 

 

Clears when the battery voltage returns to an

 

 

 

 

 

acceptable level.

 

 

 

 

 

Battery Voltage

W

Engine starting battery voltage falls below

Check the battery rating and

Low

 

12.5 VDC for more than 90 seconds when the

condition.

 

 

engine is not running.

Check the battery charger operation.

 

 

Not operative during the engine crank cycle.

 

 

Charge or replace the battery.

 

 

Clears when the battery voltage returns to an

 

 

 

acceptable level.

 

 

 

 

 