3.2.1Controller Keypad

The RUN, OFF, and AUTO buttons control the generator set as described in Figure 3-3.

Use the Select, Up arrow, and Down arrow buttons to navigate through the menus and change settings, if necessary. See Section 2.4 for operation instructions.

3.2.2LED Indicators

LEDs above the RUN, OFF, and AUTO buttons indicate the mode of operation as shown in Figure 3-4.

Load indication LEDs indicate the load on the generator set. A steadily lighted LED indicates that the load on the generator set is greater than or equal to the level label for that LED. The next LED flashes and stays on for a longer time as the load increases.

Button

 

Button Function

 

 

 

RUN

 

Starts the generator set. The engine start time delay is ignored.

 

 

 

OFF

 

Stops the generator set. The cooldown time delay is ignored.

 

 

During the engine crank cycle, pressing OFF will stop the crank cycle.

 

 

Press OFF to clear faults and reset the controller.

 

 

 

AUTO

 

Places the generator set in Automatic (standby) mode.

 

 

 

Down arrow

 

Use to navigate through menus and change settings. This manual contains instructions

 

 

to navigate the controller menus and adjust settings on the VSC controller.

Select

 

 

 

 

 

 

Up arrow

 

 

 

 

 

Figure 3-3

VSC Controller Pushbutton Operation

 

 

 

LED

 

LED Operation

 

 

 

RUN

 

Lights when the generator set has been started locally by pressing the RUN button.

 

 

Remote start and stop commands are ignored.

 

 

 

OFF

 

Lights for 2 seconds, then flashes every 2 seconds when the generator set and controller

 

 

are off. Remote start/stop commands have no effect. The exercise cycle will not run.

 

 

 

 

 

In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required.

 

 

Identify and correct the fault condition before resetting the controller.

 

 

 

AUTO

 

Lights when the generator is in automatic (standby) mode. Generator set will respond to

 

 

engine start and stop commands from the controller (for example, exercise start and stop

 

 

commands) or an ATS. Time delays operate as described in Section 2.4.

 

 

 

25% load

 

LED flashes and stays on longer as load increases from 1% to 25%.

 

 

 

50% load

 

LED flashes and stays on longer as load increases from 26% to 50%.

 

 

 

75% load

 

LED flashes and stays on longer as load increases from 51% to 75%.

 

 

 

100% load

 

LED flashes and stays on longer as load increases from 76% to 100%.

 

 

 

Figure 3-4

VSC Controller LED Operation

24 Section 3 VSC Controller Operation