Load Limit =

KPS_104

Figure 3-17Effect of Changing the System Voltage Setting

Auto Stop Load: The auto stop load is set as a percentage of full load. As the battery bank approaches the fully charged state, the charge rate slows, and the load on the generator set decreases. The 6VSG will automatically stop when the load has reached or fallen below the Auto Stop Load setting for 180 seconds (3 minutes). The default setting is 40% load.

Load Limit (%): This setting limits the current output to the maximum charge rate specified by the battery manufacturer or load in the application. The default setting is 100%, which gives the maximum current values shown in Figure 3-18.Refer to the battery manufacturer's recommended maximum charge rate and contact an authorized Kohler distributor or dealer if the setting needs to be changed.

Load Limit =

(Recommended charging voltage (VDC) x Maximum charging current (amps)) x 100

 

 

 

 

 

 

 

6000 watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Voltage

 

24V

36V

48V

 

 

 

 

 

 

 

 

 

System Voltage, VDC

 

27

40.5

54

 

 

 

 

 

 

 

 

Maximum Current at 100% Load Limit, Amps

222

148

111

 

 

 

 

 

 

 

 

 

Figure 3-18Maximum Charge Current at Default Load Limit Setting of 100%