3.16.2Networking Configuration Submenu (OnCue® Password)

The networking Configuration menu includes settings used for communication with the Kohler® OnCue® Generator Management System. See Figure 3-23.

For most applications, DHCP is enabled and the IP settings cannot be changed from the controller keypad. If DHCP is enabled, IP parameters are not displayed.

If DHCP is disabled (i.e., if a static IP address is required), then the IP parameters can be modified. For applications that require static IP addresses, press and hold the select button to enable editing, disable DHCP, and then step to the next parameters and enter the information.

If an error occurs while setting a parameter, an error message is displayed and then the controller exits the edit mode. Previous settings are preserved.

Password

For the initial OnCue® setup, you will be required to reset the OnCue® password on the VSC controller, and then enter it into the OnCue® software. To reset the password, follow the instructions in Section 3-22.

Note: The password is displayed for only 10 seconds. Be sure to write down the password and serial number.

A new password is generated each time the reset password procedure is performed. If the password is reset after the OnCue® system has been set up, the connection will be lost. Enter the new password in OnCue® to reconnect.

Networking---->

Information

Networking---->

Status

Networking

Configuration

Reset OnCue Password

HOLD

Reset OnCue

Password? No

UP arrow for YES,

Down arrow for NO.

DHCP:

Enabled

<---- Return

Reset OnCue

Password? Yes

Press Select to enter YES or NO as displayed. New password is displayed for approximately 10 seconds.

S/N: 1234567

New PW: 12345

tp6804

Figure 3-23Network Configuration Submenu

TP-6843 1/13

Section 3 VSC Controller Operation 39

Page 39
Image 39
Kohler 48VDC, 6VSG, 24VDC, 36VDC manual Networking Configuration Submenu OnCue Password