3.17 Programmable Interface Module (PIM) Status Menu

Note: The PIM status menu appears if a programmable interface module (PIM) or a communications kit interface board (IB) is connected.

The PIM status menu displays the status of inputs and outputs connected to the programmable interface module (PIM) or communications kit interface board (IB). See Figure 3-26.This is a status display menu only. Input and output settings cannot be changed from the VSC controller’s user interface.

A personal computer running Kohler® SiteTechsoftware is required to change the input and output settings for the PIM. Contact an authorized distributor or dealer for service.

The Kohler® OnCue® Management System can be used to turn the PIM outputs on and off. See the OnCue® Software Operation Manual for instructions.

The input and output settings for the communications kit interface board are factory set and locked.

PIM

*

PIM 1

---->

Status:

 

 

 

 

 

<---- Return

Input 1

In/Active

Input 2

In/Active

Output 1: In/Active

Output 2:

In/Active

Output 3: In/Active

Output 4: In/Active

Output 5: In/Active

Output 6: In/Active

<---- Return

*PIM Status displays the interface board status if the optional communications kit with factory-installed interface board is installed.

Figure 3-26Programmable Interface Module (PIM) Status Menu

42 Section 3 VSC Controller Operation

TP-6843 1/13

Page 42
Image 42
Kohler 36VDC, 6VSG, 24VDC, 48VDC manual Programmable Interface Module PIM Status Menu