ION 7500 / ION 7600 User’s Guide

I/O Specifications

 

 

NOTE

Because mechanical relays have limited lifetimes, mechanical KYZ relays are typically not suitable for energy pulsing applications. For energy pulsing applications, consider using Form A outputs in KYZ mode.

A typical connection and operational details are illustrated below..

N/ON/C

R X1 R X2 R X3

Operational Block Diagram

STATE

RX1 – RX2

RX2 – RX3

 

 

 

Inactive

Open

Closed

 

 

 

Active

Closed

Open

 

 

 

Pulse

Closed for

Open for duration

duration of pulse

of pulse

 

 

 

 

R 11 R 12 R 13 R 21 R 22 R 23 R 31 R 32 R 33

NOTE

The mechanical relays should be protected by external fuses.

Rear View of Meter

Standard I/O

Solid-State relays

Solid-State Relay Outputs

Specifications for the four digital relay (Form A) outputs (D1 through D4) are as follows:

Specification

Value

 

 

Signal Type

Continuous or pulse 1

Maximum Load Voltage

30V

 

 

Maximum Load Current

80 mA

 

 

Isolation

5,000 Vrms

 

 

Scan Time

½ cycle

 

 

Connection Type

Captured-wire

 

 

Wire Type

AWG 28 to AWG 16

 

 

1Digital output D4 is configured at the factory to emit pulses for calibration testing purposes.

Chapter 6 - Hardware Reference