Multi-Tech Systems 7500, 7600 manual Voltage Magnitude Default Measurements

Models: 7500 7600

1 372
Download 372 pages 61.31 Kb
Page 305
Image 305

ION 7500 / ION 7600 User’s GuideMagnitude of Voltage Supply

Voltage Magnitude Default Measurements

Register

Source Module Type

Description

 

 

 

V1-Mag N*

 

number of valid intervals (voltage on phase 1 within +/- 15% of nominal)

 

 

 

V1-Mag N invld*

 

number of invalid intervals

 

 

 

V1-Mag N1*

 

number of valid intervals in which the voltage deviates from nominal by more than +/-10%

 

 

 

V2-Mag N*

 

number of valid intervals (voltage on phase 2 within +/- 15% of nominal)

 

Signal Limit Evaluation

 

V2-Mag N invld*

number of invalid intervals

 

 

 

V2-Mag N1*

 

number of valid intervals in which the voltage deviates from nominal by more than +/- 10%

 

 

 

V3-Mag N*

 

number of valid intervals (voltage on phase 3 within +/- 15% of nominal)

 

 

 

V3-Mag N invld*

 

number of invalid intervals

 

 

 

V3-Mag N1*

 

number of valid intervals in which the voltage deviates from nominal by more than +/- 10%

 

 

 

PO V1-Mag N

 

V1-Mag N of the previous Observation Period

 

 

 

PO V1-Mag N1

 

V1-Mag N1 of the previous Observation Period

 

 

 

PO V2-Mag N

Store

V2-Mag N of the previous Observation Period

 

 

PO V2-Mag N1

V2-Mag N1 of the previous Observation Period

 

 

 

 

PO V3-Mag N

 

V3-Mag N of the previous Observation Period

 

 

 

PO V3-Mag N1

 

V3-Mag N1 of the previous Observation Period

 

 

 

V1 mean

Sliding Window Demand

average voltage on phase 1 over 10m (used for display purposes)

 

 

 

V1 mean mn

Minimum

minimum of average voltage V1 (V1 mean) over 1 week (used for display purposes)

 

 

 

V1 mean mx

Maximum

maximum of average voltage V1 (V1 mean) over 1 week (used for display purposes)

 

 

 

V2 mean

Sliding Window Demand

average voltage on phase 2 over 10m (used for display purposes)

 

 

 

V2 mean mn

Minimum

minimum of average voltage V2 (V2 mean) over 1 week (used for display purposes)

 

 

 

V2 mean mx

Maximum

maximum of average voltage V2 (V2 mean) over 1 week (used for display purposes)

 

 

 

V3 mean

Sliding Window Demand

average voltage on phase 3 over 10m (used for display purposes)

 

 

 

V3 mean mn

Minimum

minimum of average voltage V3 (V3 mean) over 1 week (used for display purposes)

 

 

 

V3 mean mx

Maximum

maximum of average voltage V3 (V3 mean) over 1 week (used for display purposes)

 

 

 

V1-Mag N1/N

 

N1/N ratio

 

 

 

V2-Mag N1/N

 

N1/N ratio

 

 

 

V3-Mag N1/N

Arithmetic

N1/N ratio

 

 

PO V1-Mag N1/N

N1/N ratio of the previous Observation Period

 

 

 

 

PO V2-Mag N1/N

 

N1/N ratio of the previous Observation Period

 

 

 

PO V3-Mag N1/N

 

N1/N ratio of the previous Observation Period

 

 

 

* This data is recorded once a week by Data Recorder module 17.

Power Quality: ION Meters and EN50160 Technical Note

Page 305

Page 305
Image 305
Multi-Tech Systems 7500, 7600 manual Voltage Magnitude Default Measurements, Register Source Module Type Description