ION 7500 / ION 7600 User’s Guide

Data Logging Setup

 

 

Data Logging Setup

The data recording frameworks contain Data Recorder modules, Waveform Recorder modules, and Periodic Timer modules. Data Recorder and Waveform Recorder modules are responsible for logging the power system data. The Periodic Timer modules control the recording frequency of the recorder modules to which they are linked.

Default Logging Capacity

The following table summarizes the default recording depths and recording intervals of the various Data recorders and Waveform recorders in the meter.

Log name

Depth

 

Interval

 

 

 

 

Revenue Log

3360

 

900 seconds (15 minutes)

 

 

 

 

Loss Log

3360

 

900 seconds (15 minutes)

 

 

 

 

TOU Data Logs (6 data recorders)

20

(ION 7500)

Triggered on demand

50

(ION 7600)

 

 

 

 

 

 

Historic Logs (3 data recorders)

760

 

900 seconds (15 minutes)

 

 

 

 

Harmonics Logs (2 data recorders)

190

(ION 7500)

3600

840

(ION 7600)

 

 

 

 

 

 

Waveform recording (waveform recorders:

5

ION 7500)

Triggered on demand

6 for ION 7500, 14 for ION 7600)

15

(ION 7600)

 

 

 

 

 

Report Generator Log (EgyDmd Log)

192

ION 7500)

900 seconds (15 minutes)

3360

(ION 7600)

 

 

 

 

 

 

Sag/Swell Log

100

 

Triggered on demand

 

 

 

 

Transient Log (ION 7600 only)

100

 

Triggered on demand

 

 

 

 

Event Log (Event Log Controller module)

500

 

Triggered on demand

 

 

 

 

EN50160 Logs (22 data recorders)

10

 

Daily, weekly, 10 minutes, ...

(ION 7600 only)

 

 

 

 

 

 

 

 

Procedures for changing the logging depth and the frequency of logging are follow below.

Changing the Log Depths

Change the value in the Data Recorder’s Depth setup register to increase the number of records stored in the recorder. The RecordMode setup register controls how the Data Recorder will overwrite old records; refer to the Data Recorder module description in the online ION Programmer’s Reference before changing this setup register.

Chapter 3 - Default Meter Functionality