Multi-Tech Systems 7500 Power Frequency Default Measurements, Source Module Type Description

Models: 7500 7600

1 372
Download 372 pages 61.31 Kb
Page 303
Image 303

ION 7500 / ION 7600 User’s GuidePower Frequency

Power Frequency Default Measurements

Register Label

Source Module Type

Description

 

 

 

Freq N*

 

number of valid intervals (voltage on all phases within +/- 15% of nominal)

 

 

 

Freq N invld*

Signal Limit Evaluation

number of invalid intervals

 

 

Freq N1*

number of valid intervals in which the freq deviates from the nominal by more than +/-1%

 

 

 

 

Freq N2*

 

num of valid intervals in which the freq deviates from the nominal by more than +4% or -6%

 

 

 

PO Freq N

 

Freq N of the previous Observation Period

 

 

 

PO Freq N1

Store

Freq N1 of the previous Observation Period

 

 

 

PO Freq N2

 

Freq N2 of the previous Observation Period

 

 

 

Freq mean-ep

Sliding Window Demand

average Frequency over 10s (used for display purposes)

 

 

 

Freq mn-op

Minimum

minimum mean Frequency (Freq mean-ep) over 1week (used for display purposes)

 

 

 

Freq mx-op

Maximum

maximum mean Frequency (Freq mean-ep) over 1week (used for display purpose)

 

 

 

Freq N1/N

 

N1/N ratio

 

 

 

Freq N2/N

Arithmetic

N2/N ratio

 

 

PO Freq N1/N

N1/N ratio of the previous Observation Period

 

 

 

 

PO Freq N2/N

 

N2/N ratio of the previous Observation Period

 

 

 

* This data is recorded once a week by Data Recorder module 17.

Optionally, the data below can be recorded every 10 minutes by Data Recorder 32.

Register Label

Description

 

 

PQ Freq mean

average Frequency over 10minutes

 

 

PQ Freq low

minimum Frequency over 10 minutes (HS measurement)

 

 

PQ Freq high

maximum Frequency over 10 minutes (HS measurement)

 

 

Power Quality: ION Meters and EN50160 Technical Note

Page 303

Page 303
Image 303
Multi-Tech Systems 7500 Power Frequency Default Measurements, Source Module Type Description, Register Label Description