Top Vent Configuration with Vertical Termination

30

Installation (for qualified installers only)

Top Vent Configuration with Vertical Termination

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and

diffuser positions.

40' (max)

Up to four elbows (45° or

 

90°) may be used.

 

Only one horizontal elbow

35 feet

may be used.

 

May use 8" or 6-5/8"

 

diameter vent (see page for

 

21 details).

30 feet

 

25 feet

20 feet

15 feet

10 feet

5 feet

0 feet

H2

This is considered a horizontal

elbow (it does not matter Manual background whether it turns right or left).

It may be a 90° or 45° elbow.

H1

0feet

5feet

10feet

15feet

20'(max)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exhaust Restrictor # 6

Intake Restrictor # 2

Diffuser Position # 2

Exhaust Restrictor # 5

Intake Restrictor # 2

Diffuser Position # 2

0feet

5feet

10feet

15feet

20'(max)

Horizontal length is calculated by adding both lengths of horizontal run Manual background (Horizontal Length = H1 + H2).