35.DIGITAL INPUT #5 FUNCTION
USE PARAMETER #35 TO SELECT THE #5 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0005h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0005h, which is a reverse input which must have +24VDC applied with respect to TB2:A 1 to be active.
36.DIGITAL INPUT #6 FUNCTION
USE PARAMETER #36 TO SELECT THE #6 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0006h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0006h, which is the frequency mode input which must have +24VDC applied with respect to TB2:A 1 to be active.
37.DIGITAL INPUT #7 FUNCTION
USE PARAMETER #37 TO SELECT THE #7 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0007h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0007h, which is a local/remote input which must have +24VDC applied with respect to TB2:A 1 to activate remote.
38.DIGITAL OUTPUT #1 FUNCTION
USE PARAMETER #38 TO SELECT THE #1 DIGITAL OUTPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0004h no decimal significance
VL4 and VL2 are always 00. VL3 determines the function of the output. The following have been predefined:
00h General Purpose Output
01h No Fault Output
02h At Speed Output
03h Remote Output
04h Run Hold
05h Zero Speed
06h Set by comm
07h Contactor
08h through 0Fh - Not Assigned, selection will cause output to be General Purpose Output.
ANY DIGITAL OUTPUT MAY BE ASSIGNED ANY FUNCTION. The factory defaults are included for testing purposes, to provide a baseline setup, and to be able to run the
VL3 contains the sense flag, which is either 00h or 01h. A 01h setting means that contact between the output terminals will be closed when the output function is active (a normally open contact). A 00h setting in VL3 means that the contact will be closed when the function is not active (a normally closed contact).
A General Purpose Output may be controlled by the program or communications.
The default, by factory setting, is 0001 0004h, which is a run output which is a closed output contact when the run is active (true). This is normally used as a run hold contact, but it may be used as a run output contact for some other purpose if the run signal is maintained, rather than a momentary