1.0CONNECTIONS
POWER CONNECTIONS:
POWERTEC Brushless DC motor controllers are supplied with nominal input voltages of 230, 380, and 460VAC. Three phase input power is required. The input is not phase sensitive. Connect the appro- priate power supply to the input fuses at L1, L2, and L3 (check nameplate for proper input voltage and capacity).
Connect the output terminals T1, T2, and T3 to the respective terminals on the Brushless DC motor. It is very important that the T1 terminal on the motor connects to T1 on the drive, T2 of the motor connects to T2 of the drive, and T3 of the motor connects to T3 of the drive. An earth ground wire of the same gauge as the motor power leads or one gauge smaller (no smaller than #14 AWG) must be run from a bolt
Motor |
| Orange | |
1 | |||
Brown | |||
| 2 | Red | |
| 3 | ||
| Blue | ||
T1 | 4 | ||
Yellow | |||
| 5 | ||
T2 | Black | ||
6 | |||
Green | |||
| 7 | ||
T3 | Purple | ||
8 | |||
White | |||
| 9 | ||
| Shield | ||
| 10 | ||
|
|
in the motor junction box to the ground terminal on the drive. A wire must then be run from the ground terminal on the drive (next to the motor terminals) to an earth ground at or near the power source. The Model 1000 drive does not have the common circuitry connected to earth ground (chassis). In most cases this works best, but in some cases it does not. POWERTEC recommends connecting a short jumper wire from the drive common at any one of the several places available on the terminal strips to a nearby point on the drive chassis or backpanel that will establish this ground. This is more important in applications where multiple drives are connected together or serial communications from a host are used. All other POWERTEC drives have the common grounded by mounting screws on the regulator boards.
Run
Stop
Fwd Rev
RS-485
Communications
POWERTEC
Brushless
DC Drive
G
T3
T2
T1
L3
L2
L1
HALL SHIELD | HS1 | HS3 | HS2 | HS4 | HS5 | HALL COMMON | HALL POWER | THERMAL | THERMAL POWER | Spacer |
| 24V COMMON | Digital Input COMMON Cathodes | Digital In 1 | Digital In 2 | Digital In 3 | Digital In 4 | Digital In 5 | Digital In 6 | Digital In 7 | FREQ REF IN+ | FREQ IN- FREQ REF SHIELD +24V | Spacer |
| COMMUNICATIONS+ | COMMUNICATIONS- | COMMUNICATIONS SHIELD | COMMUNICATIONS COMMON |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
A | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
| A | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
| A | 1 | 2 | 3 | 4 | |
TB1 |
|
|
|
|
|
|
|
|
|
| TB2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| TB3 |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Board | |||||
B | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
| B | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
| B | 1 | 2 | 3 | 4 | |
| Analog In COMMON | +10VDC | Analog In 1+ | Analog In 1- | Analog In 2+ | Analog In 2- | Analog Out 1+ | Analog Out 2+ | Analog Out COMMON | Spacer |
| +24V | Digital Out 1A | Digital Out 1B | Digital Out 2A | Digital Out 2B | Digital Out 3A | Digital Out 3B | Digital Out 4A | Digital Out 4B | FREQ REF OUT+ | FREQ REF OUT- | FREQ REF COMMON SPEED OUT Speed Out COMMON | Spacer |
| DISPLAY POWER | DISPLAY + | DISPLAY- | Display COMMON |
|
Analog
Speed Pot
|
|
|
|
|
| KDU Cable is | |
| 1 | 2 | 3 | 4 |
| ||
Keypad | Belden # 9463 | ||||||
“Blue Hose” or | |||||||
Display | |||||||
Unit | equivalent |
Figure 3: Basic connections to the DFS-1 controlled settings for some of the inputs and outputs. Note that will require a change in the DFS-1 setup.
POWERTEC Brushless DC motor control, using the factory default the speed pot input is the default, and that using the 4-20mA input