29.ANALOG OUTPUT #2 LOW ENGINEERING UNITS (EGU)

USE PARAMETER #29 TO SELECT THE THRESHOLD OF ANALOG OUTPUT #2 EFFECT. RANGE OF VALUES: FFFE 7961h to 0001 869Fh

-99,999 to +99,998 (dec.)

Default Value: 0000 0000h

0 (decimal)

(See Parameter 14 for the definition

and purpose of EGU)

Parameter #29 sets the point, in EGU’s, at which the Analog Output #2 will be -10VDC.

30.ANALOG OUTPUT #2 HIGH ENGINEERING UNITS (EGU)

USE PARAMETER #30 TO SELECT THE MAXI- MUM ANALOG OUTPUT #2 EFFECT.

RANGE OF VALUES: FFFE 7961h to 0001 869Fh -99,999 to +99,998 (dec.)

Default Value: 0000 0096h

150 (decimal)

If parameter #30 is greater on the absolute scale than parameter #29, the voltage at Analog Output #2 will be proportionally scaled from the low EGU’s (#29) to +10VDC at the high engineering units

(#30).

If parameter #30 is less than parameter #29 on the absolute scale, then the sense of the output will be inverted, i.e., the higher voltage (on an absolute scale from -10VDC to +10VDC) will be present at the low EGU setting (parameter #29) and the lower voltage will be output at the high EGU setting (parameter #30).

Low EGU

High EGU

Speed

Vout

 

 

 

 

 

0

+1750

 

0

-10

 

 

 

 

 

0

+1750

1750

(FWD)

+10 VDC

 

 

 

 

0

+1750

1750 (REV)

0 VDC

 

 

 

 

 

-1750

+1750

 

0

0 VDC

 

 

 

 

 

-1750

+1750

1750

(FWD)

+10 VDC

 

 

 

 

-1750

+1750

1750 (REV)

-10 VDC

 

 

 

 

 

-100

+400

 

0

-6 VDC

 

 

 

 

 

+400

-100

 

0

+6 VDC

 

 

 

 

 

+1750

0

875

(FWD)

+5 VDC

 

 

 

 

 

Table of Values for Analog Outputs

Page 28

DFS-1 Manual

Revised 7/95

 

 

POWERTEC Ind. Corp.©