31.DIGITAL INPUT #1 FUNCTION
USE PARAMETER #31 TO SELECT THE #1 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0001h no decimal significance
VL4 and VL2 are always 00. VL1 determines function of the input. The following are predefined:
| 00h | General Purpose Input | 
| 01h | Run Input | 
| 02h | Preset Input | 
| 03h | Up Input | 
| 04h | Down Input | 
| 05h | Reverse Input | 
| 06h | Frequency Mode | 
| 07h | Remote Input | 
| 08h | Master/Slave (not functional at present) | 
| 09h | Jog | 
| 0Ah | Preset 2 | 
| 0Bh | Contactor Aux | 
| 0Ch | through 0Fh Not Assigned, selection | 
| 
 | will cause input to be General Purpose | 
| 
 | Input. | 
Any digital input may be assigned to any function. The factory defaults are included for testing purposes, to provide a baseline setup, and to be able to run the 
VL3 contains the polarity flag, which is either
00h or 01h. A 01h setting means that +24VDC must be applied to the input to make it active. A 00h setting means the input is active with no voltage applied.
A Digital Input may get its +24VDC signal from any source with TB2:A1 common, and may be any parameter, transducer, or switch at which the pro- gram or communications wishes to look.
The default, by factory setting, is 0001 0001h, which is a run input which must have +24VDC applied with respect to TB2:A1 to be active.
32.DIGITAL INPUT #2 FUNCTION
USE PARAMETER #32 TO SELECT THE #2 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0002h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0002h, which is a preset input which must have +24VDC applied with respect to TB2:A1 to be active.
33.DIGITAL INPUT #3 FUNCTION
USE PARAMETER #33 TO SELECT THE #3 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0003h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0003h, which is an UP (increase) input which must have +24VDC applied with respect to TB2:A to be active.
34.DIGITAL INPUT #4 FUNCTION
USE PARAMETER #34 TO SELECT THE #4 DIGITAL INPUT FUNCTION.
RANGE OF VALUES: 0000 0000h to 0001 000Fh no decimal significance
Default Value: 0001 0004h no decimal significance
The setting options are the same as parameter #31. The default, by factory setting, is 0001 0004h, which is an DOWN (decrease) input which must have +24VDC applied with respect to TB2:A1 to be active.
| Revised 7/95 | Page 29 | |
| POWERTEC Ind. Corp.© | 
 | 
 | 