Header

46

Header

Deflection

 

Header Span (ft.)

 

Depth

 

4’

6’

8’

10’

 

L/480

740*

385*

229*

142*

12”

 

 

 

 

 

L/360

740*

385*

229*

142*

 

 

 

 

 

 

 

L/240

740*

385*

229*

142*

 

 

 

 

 

 

 

L/480

798*

574*

385*

311*

18”

 

 

 

 

 

L/360

798*

574*

385*

311*

 

 

 

 

 

 

 

L/240

798*

574*

385*

311*

 

 

 

 

 

 

 

L/480

886*

629*

429*

361*

24”

 

 

 

 

 

L/360

886*

629*

429*

361*

 

 

 

 

 

 

 

L/240

886*

629*

429*

361*

 

 

 

 

 

 

* indicates ultimate load divided by 3 for the design capacity.

In all cases where a concentrated load is placed over on opening or the design loads exceed the capacity of a panel header, Premier Insul-Beam II should be used if possible or an engineered header assembly is required. More information on this chart can be found in Technical Bulletin #10 (www.pbssips.com).

Continuous over opening

Load Chart 7:

Allowable Header Loads (plf)

Condition 1–Panel is Continuous

Over Opening (No Splines)

Page 46
Image 46
Premier Floors manual Header