Serial Protocols
RS400 77 ROS™ v3.5
Forward Exceptions
Synopsis: { Disabled, Enabled }
Default: Enabled
When the Master polls for an unconfigured RTU or the remote Modbus Server receives a poll
for an RTU which is not configured or is timing out, it returns an exception message. Enabling
this feature forwards these messages to the Master as exception codes 10 (no path) and 11 (no
response). Disable this feature if your Master is confused by these codes and would prefer to
time-out when a failure occurs.
Link Stats
Synopsis: { Disabled, Enabled }
Default: Enabled
Enables links statistics collection for protocol.
DSCP
Synopsis: 0 to 63
Default: 0
DSCP - Differentiated Services Code Point, to set the DS byte in the IP header. DS byte setting
is supported in the egress direction only.
2.3.6 WIN and TIN
Figure 48: WIN and TIN Form