2 Serial Protocols

RuggedCom devices support following serial protocols:

Raw Socket serial encapsulation

Preemptive Raw Socket

TCPModbus (client and server modes)

DNP 3

Microlok

WIN and TIN

Mirrored Bits

2.1Serial Protocols Overview

Baud rates on serial interfaces can be configured in range of 100 to 230400 bps. A “turnaround” time is supported to enforce minimum times between messages sent out the serial port.

If port is set to force half duplex mode, while sending data all received data will be discarded. To set this mode, port must natively work in full duplex mode.

To transport protocol messages through the network, either TCP/IP or UDP/IP transport can be used. The exception is TCPModbus protocol that can not be employed over UDP.

The setting of Differentiated Services Code Point (DSCP) in the IP header is provided for TCP/IP and UDP/IP transport in the egress direction only.

Debugging facilities include statistics and tracing information on a serial port and/or network transport.

2.1.1‘Raw Socket’ protocol features

A means to transport streams of characters from one serial port, over an IP network to another serial port

XON/XOFF flow control

Configurable local and remote IP port numbers per serial port

Point-to-point UDP transactions

TCP accept or request connection mode

Point-to-point TCP connection mode and a broadcast connection mode in which up to 64 remote servers may connect to a central server

Packetization and sending data on a full packet, a specific character or upon a timeout

Configurable “turnaround” time to enforce minimum time between messages sent out the serial port.

2.1.2Preemptive Raw Socket’ protocol features

A means to transport streams of characters from one serial port, over an IP network to another serial port

Configurable local and remote IP port numbers per serial port

TCP accept or request one permanent connection on configured IP address