Serial Protocols

Figure 54: Device Address Form

Protocol

Synopsis: { ModbusServer, ModbusClient, DNP, WIN, TIN, MicroLok }

Default: ModbusServer

The serial protocol supported on this serial port.

Address

Synopsis: Any 31 characters

Default:

The destination (source) device address. Could be local or remote. Local address is the address of the device connected to the serial port on this device, and serial port must be configured. Remote address is the address of the device connected to the remote host's serial port. In that case RemoteIpAddr must be configured. NOTE: The range and format of the address is defined by protocol:

Modbus: 1 to 244

MicroLok: 1 to 65535, or 8 to hexadecimal digits ‘1’ to ‘a’

DNP 3.0: 1 to 65520

WIN: 6 bits address (0 to 63)

TIN: String 'wdr' for wayside data radio (TIN mode 2), or 32 bits address, 8 digits, allowed are hexadecimal digits '0' to 'f'. All zeros are not allowed.

Remote IP Addr

Synopsis: ###.###.###.### where ### ranges from 0 to 255

Default:

The IP address of remote host where device with configured remote address is connected.

Port

Synopsis: 1 to maximum port number or {Unknown}

ROS™ v3.5