Serial Protocols
ROS™ v3.5 84 RS400
Figure 54: Device Address Form
Protocol
Synopsis: { ModbusServer, ModbusClient, DNP, WIN, TIN, MicroLok }
Default: ModbusServer
The serial protocol supported on this serial port.
Address
Synopsis: Any 31 characters
Default:
The destination (source) device address. Could be local or remote. Local address is the address
of the device connected to the serial port on this device, and serial port must be configured.
Remote address is the address of the device connected to the remote host's serial port. In that
case RemoteIpAddr must be configured. NOTE: The range and format of the address is defined
by protocol:
Modbus: 1 to 244
MicroLok: 1 to 65535, or 8 to hexadecimal digits ‘1’ to ‘a’
DNP 3.0: 1 to 65520
WIN: 6 bits address (0 to 63)
TIN: String 'wdr' for wayside data radio (TIN mode 2), or 32 bits address, 8 digits, allowed are
hexadecimal digits '0' to 'f'. All zeros are not allowed.
Remote IP Addr
Synopsis: ###.###.###.### where ### ranges from 0 to 255
Default:
The IP address of remote host where device with configured remote address is connected.
Port
Synopsis: 1 to maximum port number or {Unknown}