Sanyo SAP-CMRV1426EH-F, SAP-CMRV1926EH service manual SAP-CMRV2446EH, SAP-KMRV96EH ⋅

Models: SAP-CMRV1926EH SAP-CMRV1426EH-F

1 148
Download 148 pages 30.45 Kb
Page 10
Image 10
SAP-CMRV2446EH

Outdoor Unit

SAP-CMRV2446EH

 

 

 

 

 

 

Indoor Unit

SAP-KMRV96EH 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

 

4-Room Multi Outdoor Unit

Number of Connectable Indoor Units

 

 

 

4

 

Number of Operatable Indoor Units

 

 

 

4

 

Max. Capacity of Operating Indoor Units

kW

 

 

13.1

 

 

 

 

 

 

 

 

 

Power Source

 

 

 

 

220 to 240V Single-Phase 50Hz

 

 

 

 

 

 

 

 

 

Voltage Rating

 

 

 

 

230V

 

 

 

 

 

 

 

 

 

 

 

Performance

 

 

 

 

Cooling

 

 

Heating

 

Capacity

 

 

kW

6.8

( 2.9 to 8.1 )

 

8.6

( 3.4 to 9.0 )

 

 

 

 

BTU/h

23,200

( 9,900 to 27,600 )

 

29,300

( 11,600 to 30,700 )

 

Air Circulation (High)

 

m3/h

 

2,700

 

 

2,700

 

 

 

 

 

 

 

 

 

Electrical Rating

 

 

 

Cooling

 

 

Heating

 

Available Voltage Range

V

 

198 to 264

 

 

Running Amperes

 

A

 

8.87

 

 

8.87

 

Power Input

 

 

W

 

2,000

 

 

2,000

 

Power Factor

 

%

 

98

 

 

98

 

E.E.R.

 

 

W/W

 

3.40

 

 

-

 

C.O.P.

 

 

W/W

 

-

 

 

4.30

 

Compressor Locked Rotor Amperes

A

 

 

14.5

 

 

 

 

 

 

 

 

 

 

Features (Outdoor Unit)

 

 

 

 

 

 

 

 

Controls

 

 

 

 

Microprocessor

 

 

Fan Speeds

 

 

 

 

Auto (Hi, Me, Lo)

 

 

Compressor

 

 

 

 

DC Twin Rotary (Inverter)

 

Refrigerant / Amount charged at shipment

kg

 

R410A / 2.8

 

 

Refrigerant Control

 

 

 

Electric Expansion Valve

 

Operation Sound

Hi

dB-A

 

47

 

 

49

 

Refrigerant Tubing Connections

 

 

Flare

Type

 

 

Max. allowable tubing length per unit

m

 

 

25

 

 

Refrigerant

 

Narrow tube

mm (in.)

 

6.35 (1/4") 4

 

 

Tube Diameter

Wide tube

mm (in.)

 

9.52 (3/8") 3 + 12.7 (1/2") 1

 

 

 

 

 

 

 

 

 

Dimensions & Weight (Outdoor Unit)

 

 

 

 

 

 

 

Unit Dimensions

 

 

 

 

 

 

 

 

Height Width Depth

mm

 

740 900 320

 

 

Package Dimensions

 

 

 

 

 

 

 

 

Height Width Depth

mm

 

868 1,050 423

 

 

Weight

 

Net

kg

 

 

65.0

 

 

 

 

Shipping

kg

 

 

69.0

 

 

Shipping Volume

 

m3

 

 

0.38

 

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

Remarks:

1.The values shown in perfromance section and electrical rating section above are based on the following unit combination. For other combination unit, please refer to the "Unit Combination Table" in this manual.

Indoor Unit: SAP-KMRV96EH 4units

Outdoor Unit: SAP-CMRV2446EH 1unit

2. Rating conditions are: Cooling: Indoor air temp. 27°C D.B. / 19°C W.B.

Heating: Indoor air temp. 20°C D.B.

Outdoor air temp. 35°C D.B. / 24°C W.B.

Outdoor air temp. 7°C D.B. / 6°C W.B.