Sanyo SAP-CMRV1926EH, SAP-CMRV1426EH-F service manual English, Table, Connecting Indoor Units, Fig

Models: SAP-CMRV1926EH SAP-CMRV1426EH-F

1 148
Download 148 pages 30.45 Kb
Page 111
Image 111
Fig. 4a

install the indoor unit more than 1 meter away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.

install in a sturdy manner to avoid increased operating noise.

Table 3

 

Max. Allowable

Max. Allowable Total

 

Limit of

Limit of Elevation

Required Amount

 

Tubing Length

Tubing Length

Total Tubing Length

Difference

of Additional

Model

per unit

 

at shipment

(L1+L2) or (L1+L2+L3)

(H1, H2, H3, H4)

Refrigerant

 

(m)

(L1+L2) or (L1+L2+L3)

or (L1+L2+L3+L4)

(m)

(g/m)*

 

 

or (L1+L2+L3+L4)

 

(m)

 

 

 

 

 

(m)

 

 

 

 

 

 

 

 

 

 

 

 

CMRV1926

25

45

(L1+L2)

45

(L1+L2)

15

 

 

 

 

 

 

 

 

CMRV1936

25

45

(L1+L2+L3)

45

(L1+L2+L3)

15

 

 

 

 

 

 

 

 

CMRV2446

25

45

(L1+L2+L3+L4)

60

(L1+L2+L3+L4)

15

20

 

 

 

 

 

 

 

 

CMRV3146

30

45

(L1+L2+L3+L4)

70

(L1+L2+L3+L4)

15

20

 

 

 

 

 

 

 

 

*If total tubing length becomes 45 to 60 m (max.) or 45 to 70 m (max.), charge additional refrigerant (R410A) by 20 g/m. No additional charge of compressor oil is necessary.

English

2-2. Connecting Indoor Units

(1) Connecting indoor unit for SAP-CMRV1926

(A)

Outdoor unit

ø9.52

B

ø9.52

ø6.35

 

ø9.52

 

A

ø9.52

ø6.35

 

Indoor unit

(SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS)

(SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS)

Fig. 4

(B)

Outdoor unit

Indoor unit

 

 

 

 

 

ø9.52

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø9.52

ø6.35

A

ø12.70

 

ø9.52

ø6.35

 

(SAP-KMRV74EH, KMRV94EH, KMRV124EH) (SAP-KMRV76EH, KMRV96EH, KMRV126EH) (SAP-KRV96EHDS, KRV126EHDS)

(SAP-KRV184EH) (SAP-KRV186EH)

Flare ø9.52 Union ø12.70

A joint for connecting tubes of different sizes

(ø9.52 Manual background ø12.70) Supplied Reducer

Fig. 4a

unit: mm

5

Page 111
Image 111
Sanyo SAP-CMRV1926EH, SAP-CMRV1426EH-F service manual English, Table, Connecting Indoor Units, Fig