Page 27
Image 27
Manual background

Outdoor Unit SAP-CMRV3146EH

Indoor unit

Outdoor unit

 

Service valve on

 

Sub

Main

Compressor

 

CW

 

accumulator

accumulator

Wide tube

wide tube

 

 

DW

 

 

 

 

O.D.9.52mm

 

 

 

 

 

O.D.9.52mm

BW

 

 

 

 

O.D.12.7mm

 

 

 

 

AW

 

 

 

 

O.D.12.7mm

 

 

 

 

Header

4-way

 

 

 

 

 

 

 

 

valve

 

exchanger

 

 

 

Defrost valve

S

 

 

 

for hot gas bypass

 

 

 

Electric

 

 

 

 

 

 

Heat

 

 

expansion

 

 

Service valve on

valve

 

 

 

 

 

 

 

narrow tube

M

 

 

 

Narrow tube

DN

 

 

 

 

 

 

 

O.D.6.35mm

CN

M

 

 

 

O.D.6.35mm

 

 

 

 

BN

M

 

 

 

 

 

 

 

O.D.6.35mm

 

 

 

 

AN

M

 

 

 

 

 

 

 

O.D.6.35mm

 

 

 

 

Strainer

 

Header

 

 

 

 

 

 

Cooling cycle

Heating cycle

Defrosting cycle

Insulation of Refrigerant Tubing

IMPORTANT

Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.

After a tube has been insulated, CAUTION never try to bend it into a narrow

curve because it can cause the tube to break or crack.

 

Insulation

Thickness:

Thickness:

Min. 8 mm

Min. 8 mm

Wide tube

Narrow tube

 

27