Sanyo SAP-CMRV1926EH English, Be sure to match refrigerant, tubing and electric wiring, units

Models: SAP-CMRV1926EH SAP-CMRV1426EH-F

1 148
Download 148 pages 30.45 Kb
Page 121
Image 121
Manual background

CAUTION

Be sure to match refrigerant

tubing and electric wiring

 

 

 

between indoor and outdoor

 

units.

3-7. Insulation of Refrigerant Tubing

IMPORTANT

To prevent heat loss and wet floors due to dripping of con-

densation, both tubes must be well insulated with a proper insulation material.

The thickness of the insulation should be a minimum 8 mm. (Fig. 17)

Torque wrench

 

Spanner

 

Indoor unit

 

Outdoor unit

English

Fig. 15

 

Insulation

 

Fig. 16

 

Insulation

 

3-8. Taping the Tubes

CAUTION

After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack.

 

Thickness:

Min.

min. 8 mm

8 mm

 

Fig. 17

(1)At this time, the 2 refrigerant tubes (and electrical wire if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.

(2)Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18)

(3)Clamp the tubing bundle to wall, using 1 clamp approx. every 120 cm.

NOTE

Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con- densation drain hose splits away from the bundle and drips clear of the unit and the tubing.

3-9. Finishing the Installation

After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19)

15

Clamp

Insulated tubes

Fig. 18

Apply putty here

Tubing

Fig. 19

Page 121
Image 121
Sanyo SAP-CMRV1926EH English, Be sure to match refrigerant, tubing and electric wiring, units, Fig, Taping the Tubes