Sanyo SAP-CMRV1926EH, SAP-CMRV1426EH-F Checking the Outdoor System, Checking the outdoor unit

Models: SAP-CMRV1926EH SAP-CMRV1426EH-F

1 148
Download 148 pages 30.45 Kb
Page 73
Image 73
8-3. Checking the Outdoor System

8-3. Checking the Outdoor System

8-3-1. Checking the outdoor unit

No.

Work procedure

Check items (unit operation)

 

 

 

1

Apply 220 V AC between terminals L and N on the

The LED (red) on the control board must illuminate.

 

outdoor unit terminal plate.

 

 

 

 

2

Short-circuit the T-RUN terminal to the COM terminal

The compressor, fan motor, 4-way valve, and solenoid

 

of TEST/T-RUN terminals.

valve (for the hot gas bypass) must turn ON.

 

 

(They turn ON about (70) seconds later after the power

 

 

is turned ON.)

 

 

 

NOTE If the above check items are okay, but the outdoor unit does not operate, there may be a faulty connection between the indoor unit and the outdoor unit.

8-3-2. Checking the defrost operation

8-3-1. Checking the outdoor unit Using forced defrost operation to check this function.

No.

Work procedure

 

Check items (unit operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Connect a dummy resistor of 39 k ohm to the outdoor

 

Non-stop defrost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

coil temperature sensor connector.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

 

 

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

LL Stop

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

CM

 

 

 

 

 

 

 

(80 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solenoid valve

 

 

 

 

 

 

5 sec.

 

 

 

 

 

 

 

10 sec.

 

 

 

(for hot gas

 

 

 

 

 

 

 

 

 

 

 

 

bypass) OFF

 

 

 

ON

 

 

 

 

 

 

OFF

 

 

 

Outdoor fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

OFF

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost start

Release

The maximum length of defrost operation is 12 minutes.

Defrost can also be released based on the below conditions for the outdoor heat exchanger sensor.

Less than 2 minutes

Not released

2 minutes or more

14 °C or higher (*1)

*1 However, the condition is (20 °C) or higher when the outdoor air temperature is below 0 °C.

73

Page 73
Image 73
Sanyo SAP-CMRV1926EH service manual Checking the Outdoor System, Checking the outdoor unit, Checking the defrost operation