8-5. Trouble Diagnosis of Fan Motor

This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor.

Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit.

Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors.

(B)When performing voltage measurement at the outdoor controller connector for (3) in the table below, the DC motor will trip and voltage output will stop approximately 10 seconds after operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor unit power, then, measure the voltage in Test Run mode.

[Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble

[Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating.

(Diagnostic procedure)

*Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor unit controller (3 locations).

 

 

Measurement location

Normal value

(1) Vs-Gnd : Between pin 1 and pin 4

DC 230V or more

or

 

Vm-Gnd : Between pin 1 and pin 4

 

(2) Vcc-Gnd : Between pin 5 and pin 4

DC 14V or more

(3) Vsp-Gnd : Between pin 7 and pin 4

After fluctuating 4 times between DC 1.7 to 6.1V

 

(1 sec. ON) and DC 0 V (1 sec. OFF), the DC

 

motor trips.

(Diagnostic results)

All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Outdoor unit controller trouble

(Replace the controller .)

(Reference) DC motor connector pin arrangement

SAP-CMRV1426EH

Pin 1: Vs (white)

Pin 2: Not used

Pin 3: Not used

Pin 4: Gnd (black)

Pin 5: Vcc (red)

Pin 6: FG (blue)

Pin 7: Vsp (yellow)

SAP-CMRV1926EH / -CMRV1936EH SAP-CMRV2446EH / -CMRV3146EH

Pin 1: Vm (red)

Pin 2: Not used

Pin 3: Not used

Pin 4: Gnd (blue)

Pin 5: Vcc (brown)

Pin 6: PG (white)

Pin 7: Vsp (orange)

[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor unit operates.

(There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller.)

[Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.

[Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.

(Remedy for symptom 3 to 5)

It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble. Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.

77

Page 77
Image 77
Sanyo SAP-CMRV1926EH service manual Trouble Diagnosis of Fan Motor, Diagnostic procedure, Measurement location Normal value

SAP-CMRV1926EH, SAP-CMRV1426EH-F specifications

The Sanyo SAP-CMRV1926EH and SAP-CMRV1426EH-F stand out in the realm of advanced climate control solutions. As part of Sanyo's renowned lineup of air conditioning systems, these models are designed to offer superior performance, energy efficiency, and enhanced comfort, catering to both residential and commercial use.

One of the main features of the SAP-CMRV1926EH is its robust cooling and heating capacity, making it an ideal choice for larger spaces or those requiring rapid temperature adjustments. The model boasts a cooling capacity of up to 19kW, while the SAP-CMRV1426EH-F offers a more compact 14kW, making it suitable for smaller environments without compromising performance. This flexibility allows users to select a model that best fits their specific needs.

Both models incorporate advanced inverter technology, which significantly enhances their energy efficiency. By adjusting the compressor speed according to the ambient temperature, inverter systems minimize power consumption while maintaining a stable indoor climate. This not only reduces electricity bills but also contributes to a lower environmental impact, aligning with modern sustainability standards.

In terms of comfort, the Sanyo SAP-CMRV1926EH and SAP-CMRV1426EH-F feature sophisticated air distribution systems. They ensure even airflow throughout the area, eliminating hotspots and providing consistent temperatures. Additionally, the models are equipped with multi-split capabilities, allowing for multiple indoor units to be connected to a single outdoor unit. This versatility is particularly beneficial for larger buildings or homes with varied room requirements.

Both models also prioritize user convenience with sophisticated control options. They offer wireless remote controls as well as compatibility with smart home systems, enabling users to program settings and monitor indoor conditions from their smartphones or tablets. This modern approach enhances user engagement and allows for greater customization of the climate control experience.

Noise levels are another consideration in the design of the SAP-CMRV1926EH and SAP-CMRV1426EH-F. These units operate quietly, ensuring that they do not disrupt the tranquility of living or working spaces. Their low-noise operation is a testament to Sanyo's commitment to creating comfortable environments without compromising on performance.

In summary, the Sanyo SAP-CMRV1926EH and SAP-CMRV1426EH-F models are distinguished by their impressive cooling and heating capacities, energy-efficient inverter technology, advanced air distribution, user-friendly controls, and quiet operation. These features make them an excellent choice for anyone seeking reliable and effective climate control solutions.